7. INSTALLATION INSTRUCTIONS
7.1 General
All gas appliances must, by law, be installed by compe-
tent persons (e.g. Corgi). Failure to install appliances
correctly could lead to prosecution.
It is in your own interest and that of safety to ensure that
the law is complied with.
The following instructions must be adhered to when the
remeha W40/60-m ECO is installed:
Gas Safety (Installation and Use) Regulations 1984 (as
amended).
Current I.E.E. Regulations for electrical installations
Local building regulations.
The Building Standards (Scotland) (Consolidation)
Regulations, by-laws of the local water undertaking.
Health and Safety Document No 635 'The Electricity at
Work Regulations 1989'.
The requirements of Guidance Note PM 5 issued by the
Health & Safety Executive 'Automatically controlled
steam and hot water boilers'.
Depending on the type and size of installation i.e. large
domestic or commercial the requirements of the follow-
ing publications should be complied with:
Domestic:
BS 5449, BS 5546, BS 6644,
BS 6891, CP 3006 and BG DM2.
Commercial:
BS 6644, BS 6700, BS 6880
Pts 1, 2 and 3, CP 342.2
IM2, IM5, IM11, IM16 and IM22.
Manufacturers Instructions must NOT be taken as over-
riding statutory obligations.
Important:
The remeha W40/60-m ECO is a certified appliance and
must not be modified or installed in any way contrary to
these "Installation and Maintenance Instructions".
7.2 Location
The remeha W40/60-m ECO may be mounted free stan-
ding (on a frame supplied) or wall mounted (on a brack-
et supplied). The floor should be level and strong
enough to support the weight of the boilers full of water.
The wall should be sound and flat and capable of sup-
porting the weight of the boiler full of water.
The following minimum clearances are required:
Front:
450 mm
Sides:
50 mm
Bottom: 250 mm
Top:
400 mm.
7.3 Dimensions of wall mounting bracket
Fig. 09 Template for wall bracket remeha W40-m ECO
A = Drill hole
A = Drill hole
Fig. 10 Template for wall bracket remeha W60-m ECO