14
remeha W40/60-m ECO
6.4.5 Forced 'HIGH' mode
By pressing the 'mode' and '
▲
' key simultaneously in
operating mode, the appliance will burn at maximum
power.
The flow temperature, however, cannot exceed the pre-
set maximum, in order to protect the appliance and the
installation.
By pressing the '
▲
' and '
▼
' keys simultaneously, the
appliance will return to operating mode, or will switch to
that mode automatically after 15 minutes.
6.4.6 Forced 'LOW' mode
By pressing the 'mode' and '
▼
' key simultaneously in
operating mode, the appliance will burn at minimum
power.
The flow temperature, however, cannot exceed the pre-
set maximum, in order to protect the appliance and the
installation.
By pressing the '
▲
' and '
▼
' keys simultaneously, the
appliance will return to operating mode, or will switch to
that mode automatically after 15 minutes.
6.4.7 Speed mode (half digits)
(On service level for the heating contractor.)
The fan speed can be read in parts in the speed mode.
- Select the service code C 1 2 (see para. 6.4.9).
- Now select the fan speed code, using the 'mode'-key
(half digits).
6.4.4 Read-out mode (with blinking dot)
Various values can be read in the read-out mode.
On user level.
- Select the read-out mode by pressing the 'mode'-key
until 1. (blinking dot) appears in the 'code'-display.
- Now select the required code, using the 'step'-key.
Code
Description
Read-out (example)
1.
Flow temperature
- 8 0
2.
Return temperature
- 7 0
3.
D.H.W. temperature
- 6 5 (with sensor)
4.
Outdoor temperature
- 0 5 (with sensor)
5.
Not applicable
- 4 0
6.
Flow temperature set point
7.
Room thermostat status
- 0 open 1 closed
and air pressure switch status
- 0 open 1 closed
8.
Flow sensor temperature
- 8 0
Code
Description
Example 4900 r/m
Fan speed
- 4 9 hundreds
Fan speed
- 0 0 units