I/O Sentinel
®
4 Installation and Operation Manual
SETUP
NOTE:
When the "Normal signal level" is set to Low = When voltage IS applied to
the input, it's considered OFF. When NO voltage is applied to the input it consid-
ered ON.
NOTE:
By enabling the ON and/or OFF monitoring and NOT enabling an
email box, the device will log the events, but not send an email. If the device is exit-
ing a OFF alarm condition, then the email addresses used will be those notified when
the OFF alarm condition was entered.
Enable Extension:
Normally not checked. This box should be checked when
paired with a second I/O Sentinel® 4 to form a “4 Channel
Bi-directional Status/Relay Extension Cord”.
Log Device:
This enables the email logging of the status.
Delay Time:
The delay is in seconds. This option specifies the wait time
from when a status/logic input changes state before an alarm
is activated.
NOTE: Set to zero when paired with another
I/O Sentinel® 4.
Alarm Led Status:
Allows the user to configure the color of the web LED when
in an alarm condition.
Scheduler:
When enabled, the user may set each input alarm to be dis-
abled or enabled by configuring the required day(s) of week
and the start and end hours and minutes.
NOTE:
After any item has been changed, you MUST press the “Save Settings” but-
ton for your changes to be saved.