6 720 610 602 GB (03.02)
32
Individual settings
Setting service functions
Only the service functions that can be set are displayed.
B
Press any button to activate the main menu.
B
Press
or
button until the arrow cursor is
pointing to Settings.
B
Press the
button.
B
Press
oder
button until the arrow cursor
is pointing to Service.
B
Press the
button.
The cursor is pointing to Display service parame-
ters.
B
Press and hold the
button (for about 5 sec-
onds) until the display shows Adjust service
parameters and the first service function to be set,
e.g. 2.0, Operating mode. If a fault has occurred,
the display will show 0.0 and the last fault.
B
Press the
or
button until the desired
service function is displayed.
B
Press the
button.
The first line of the display shows Change value.
B
Use the
or
buttons to enter the required
setting.
B
Press the
button.
The text display shows ATTENTION Store set-
tings?.
B
Press
or
to select yes or no.
B
Press
to confirm your selection.
The text display shows Please wait ... ..., and the
service function is then displayed with the new set-
ting.
B
Press the
or
button until the next func-
tion you wish to change is displayed.
-or-
B
Press the
button to exit the menu.
7.2.2
Setting the anti-cycle time
(Service Function 2.4)
This service function is only active if Service Function
2.7, automatic anti-cycle time, is deactivated.
The anti-cycle time can be set to between 0 and 15 min-
utes (is factory set to 3 minutes).
If the setting 0 is entered, the anti-cycle time is inactive.
The shortest possible anti-cycle time is 1 minute (rec-
ommended for single-pipe and hot-air heating systems).
7.2.3
Setting the maximum CH flow tempera-
ture (Service Function 2.5)
The maximum CH flow temperature can be set to
between 35˚C and 88˚C (factory setting).
7.2.4
Setting the heating output
(Service Function 5.0)
The heating output can be set to any level between min.
rated heat output and max rated heat output to limit it to
the specific heat requirements.
The factory setting is the max. rated heat output, 100 %.
B
Look up heating output in kW and corresponding
code number on the settings tables for heating out-
put (see page 48).
B
Enter the code number on the text display module.
B
Measure the gas flow rate and compare with the fig-
ures specified for the code number shown. If differ-
ent, correct code number.
7.2.5
Constant hot water cycle time
(Service Function 6.8)
In Comfort mode “ECO light off”, the hot water inside
the appliance is held constantly at the set temperature.
For that reason, the appliance switches on if the water
temperature falls below a certain temperature. In order
to prevent it switching on and off too frequently, the
constant hot water cycle time service function allows
you to set the minimum period between switching off
and on again. This function has no effect on normal
demand for hot water and relates only to the constant
hot water function in Comfort mode.
The cycle time can be set to any period between 20 and
60 minutes (is factory set to 20 minutes).
7.2.6
Variable pump settings
(Service Function 7.0)
The pump speed varies automatically to match the
water flow requirement of the system determined by the
position of thermostatic radiater valves. An automatic
by-pass must not be used.
The Service Function 7.0 is factory set to 4 which will
accommodate the majority of heating systems.
Information on the re-settings of this functions can be
found in the Service Booklet for the Engineer
number 7 181 465 347.
7.3
Setting the gas/air ratio
The appliance is set at the factory and adjustment is not
necessary.
i
If the appliance is connected to an out-
side-temperature controlled heating pro-
grammer, the anti-cycle time does not
need to be set on the appliance and is op-
timised by the programmer instead.
i
The full rated heat output is still available
for hot water or charging the hot water cyl-
inder even if the heating output has been
limited.
Summary of Contents for ICC2 combi ZWBR 11-37 ICC2
Page 51: ...6 720 610 602 GB 03 02 Appendix 51 ...
Page 102: ...7 181 465 347 01 07 50 Appendix ...
Page 103: ...7 181 465 347 01 07 Appendix 51 ...
Page 104: ...Appendix ...