HL101 Series Digital Temperature Limit Control
PARAMETERS
Keyword
Parameter
Description
Range
Units
Default
SP
Setpoint
Temperature Limit
value
r1
to
r2
°
0
r0
Hysteresis
1 to 99
°
1
r1
SP Lower Limit
0 to
r2
°
0
r2
SP Upper Limit
r1
to 999
°
999
r3
Control Reset
Aut:
automatic reset
hoL:
latch alarm, manual reset
PuP:
must power cycle to reset
hoL
c2
Output status for
Probe Error
oFF/ on
oFF
c3
Alarm energize
condition
no / Yes
no
P1
Probe
Adjustment
-30 to 30
0
P5*
Probe type
Thermocouple
Type
tcJ:
J-type thermocouple
tcK:
K-type thermocouple
tcJ / tcK
P6
Probe response
Reading Refresh
interval
0:
8 sec
1:
4 sec
2:
2 sec
3:
1 sec
2
H1
Display Reading
Display shown during
normal operation
PV:
Process Value
SP:
Setpoint
SP
H5
Keyboard
Security
Access Code
0
c0
Minimum
Stopping Time
0 to 999
1
d0
Hi or Low limit
control
Hi / Lo
Hi
* Be careful not to select the wrong sensor type.
Configuration of Parameters:
1.
Press and hold the
(SET)
button for approximately 8 seconds. Use
(▲▼)
buttons to input the
access code. Press
(SET)
to Enter.
2.
Use
(▲▼)
buttons to find the desired parameter. Once found, press
(SET)
to view or modify.
3.
Adjust parameter values by using
(▲▼)
buttons.
4.
Press the
(SET)
button to save the new value. The display will flash only the parameter keyword.
5.
Use
(▲▼)
buttons to select another parameter to modify using steps 2-4 above.
6.
To exit the programming mode, press
(SET)
and
(▼)
together. OR, wait 60 seconds for the
controller to automatically exit programming mode and show the Run display per
H1.
In case
H5
(the access code) is changed and forgotten, it can be reset to
0
by turning off control,
pressing down and holding
(SET),
and turning control back on. No other parameters will be changed.
© BriskHeat
®
Corporation. All rights reserved.
8
HL101 Series Digital Temperature Limit Control
Maintenance:
Dirt, oil, grease or other foreign matter can be removed with a damp rag and mild household
cleaners. No solvents, abrasives, petrol, or alcohol.
NOTE: The device should be unplugged prior to cleaning with a damp rag and allow to fully dry before
being energized.
Inspection:
Perform before and after use of the controller.
The cables and wires should not have any visible breaks in their insulation.
The casing and control should be free of any cuts, cracks or punctures.
Storage:
This product should be stored at room temperature in an environment with less than 80% relative
humidity.
Disposal:
This product must be recycled in accordance to 2012/19/EU Waste Electrical and Electronic
Equipment (WEEE) directive.
Anyone who reads and understands these instructions
is qualified to maintain this controller.
MAINTENANCE INSTRUCTIONS