Renovent Excellent P300 Rev. D
29
Chapter 11 Electric connections accessories
11.3 Couple through eBus contact;
DOODSSOLDQFHVHTXDODLUÀRZUDWH
A
=
Multiple switch
B
=
2-pole connector
M
=
Renovent Excellent P300 (Master)
C1 t/m C* =
Renovent Excellent P300 (Slave); couple
not more than 10 appliances through Ebus
$OO5HQRYHQWVKDYHWKHVDPHDLUÀRZUDWHVDVWKH5HQRYHQW
set as “Master”.
A maximum of 10 appliances
(1 9 Slave max.)
For M (Master):
Set parameter 13 to 0 (= factory setting).
Display shows ventilation mode 1, 2 or 3.
For C1 (Slave1):
set parameter 13 to 1 (= Slave 1).
Display always shows ventilation
PRGHƑ
Important:
Because of polarity sensitivity, always connect contacts X1-1 to X1-1 and contacts X1-2 to X1-2. Never connect X1-1 and
X1-2.
230V
50Hz
230V
50Hz
230V
50Hz
For C2 (Slave2):
Set parameter 13 to 2 (= Slave 2).
Display always shows ventilation
PRGHƑ
Step
nr.
Description
Factory
setting
Range
12
Communica-
tion type
eBus
0t ( = Opentherm)
eBus
13
eBus address
0
0 = master
1- 9 = slave 1 - 9
11.4 Connection RH (huminity) - sensor
Step
nr.
Description
Factory
setting
Range
32
Activating
RH-sensor
OFF
OFF
= not active
ON
= active
33 Sensitivity
0
+2
most ensitive
+1
Ĺ
0
default setting RH-sensor
-1
Ļ
-2
least sensitive
E
A = Renovent Excellent P300
B = Control board
C = RH (huminity) - sensor
D = Cable supplied with RH sensor
E = Duct from dwelling
C1 = brown
C2 = blue
C3 = green/yellow
230V
50Hz