10
Renovent Excellent P300 Rev. D
5.1 Installation general
Installing the appliance
1. Placing the appliance (§5.2)
2. Connecting the condensate discharge (§5.3)
3. Connecting the ducts (§5.4)
4. Electric connection
Connecting the mains power, multiple switch and, if neces-
sary, the OpenTherm/eBus coupler (§5.5)
Installation must take place under:
4XDOLW\UHTXLUHPHQWVYHQWLODWLRQV\VWHPVGZHOOLQJV
4XDOLW\UHTXLUHPHQWVEDODQFHGYHQWLODWLRQLQGZHOOLQJV
7KH UHJXODWLRQV IRU YHQWLODWLRQ RI GZHOOLQJV DQG UHVLGHQWLDO
buildings.
7KHVDIHW\UHJXODWLRQVIRUORZYROWDJHLQVWDOODWLRQV
7KH UHJXODWLRQV IRU FRQQHFWLRQ WR LQWHULRU VHZHUV LQ GZHOO
-
ings and residential buildings.
$Q\DGGLWLRQDOUHJXODWLRQVRIWKHORFDOXWLOLWLHV
7KHLQVWDOODWLRQLQVWUXFWLRQVIRUWKH5HQRYHQW([FHOOHQW
5.2 Placing the appliance
The Renovent Excellent P300 can directly be mounted to the
wall using the suspension brackets supplied for that purpose.
For a vibration-free result the appliance must be mounted to a
solid wall with a minimum mass of 200 kg/m
2
. A gypsum block
RUPHWDOVWXGZDOOGRHVQRWVXႈFH$GGLWLRQDOPHDVXUHVVXFK
as double panelling or extra studs are required in that case.
2QUHTXHVWDPRXQWLQJVXSSRUWIRUÀRRUPRXQWLQJLVDYDLODEOH
In addition, the following aspects must be taken into account.
7KHDSSOLDQFHPXVWEHSODFHGOHYHO
'ZHOOLQJVZLWKFRQVWUXFWLRQPRLVWXUHPXVWEHYHQWLODWHGQD
-
turally during a certain period!
7KHLQVWDOODWLRQURRPPXVWEHIURVWIUHH
7KHLQVWDOODWLRQURRPPXVWEHVXFKWKDWDJRRGFRQGHQVD
-
te discharge with air trap and pitch for condensate can be
made.
0DNHVXUHWKHUHLVDIUHHVSDFHRIDWOHDVWFPDWWKHIURQW
of the appliance and a free headroom of 1.8 m for cleaning
WKH¿OWHUVDQGFDUU\LQJRXWPDLQWHQDQFH
0DNHVXUHWKHUHLVDIUHHVSDFHRIDWOHDVWFPDERYHWKH
display cover so it can always be removed.
:HUHFRPPHQGQRWWRLQVWDOOWKHKHDWUHFRYHU\XQLWLQVSD
-
ces with an average high RH (for instance bathroom). That
will prevent condensation on the outside of the heat reco-
very unit.
5.4 Connecting ducts
7KHDLUH[WUDFWGXFWGRHVQRWKDYHWREH¿WWHGZLWKDFRQWURO
YDOYH7KHDSSOLDQFHLWVHOIFRQWUROVWKHDLUÀRZUDWHV
To prevent condensation on the outside of the outdoor air supply
duct and the air exhaust duct downstream of the Renovent
Excellent P300, these ducts must be provided with an external
vapour barrier as far as the appliance. If thermally insulated
piping is used here, additional insulation is not necessary.
For compliance with the maximum installation noise level
of 30 dB, it will have to be assessed for every installation
VSHFL¿FDOO\ ZKDW PHDVXUHV ZLOO EH UHTXLUHG WR OLPLW WKH
QRLVH$WOHDVWDPXႉHUZLWKDOHQJWKRIQRWOHVVWKDQ
PLVUHTXLUHGEXWDGGLWLRQDOPHDVXUHVPD\EHQHFHVVDU\
Please contact the Brink Consultancy Department if you
KDYHDQ\TXHVWLRQVRQWKLVVXEMHFW
Pay attention to crosstalk and installation noise, also for
incorporated ducts. Design the duct with separate branches to
the valves to prevent crosstalk. If necessary, the supply ducts
must be insulated, for instance when they are installed outside
the insulated envelope.
Preferably use Brink incorporated ducts. These ducts have
been developed with a view to a low duct resistance.
A duct diameter of 160 mm is required for the Renovent
Excellent P300.
5.3 Connecting the condensate discharge
The condensate discharge line for the Brink Renovent HR is fed
through the lower panel. The condensate must be discharged
through a drainpipe.
The condensate discharge comes separately with the
appliance and the installer must screw it into the underside of
the appliance. This condensate discharge connection has an
external connecting diameter of 32 mm.
The condensate discharge line can be glued to it, if necessary
using a square bend. The installer can glue the condensate
discharge in the desired position in the lower part of the
appliance. The drain must discharge under the water level in
the U-trap
Before connecting the condensate discharge to the appliance,
pour water into the U-trap to create an air trap.
Chapter 5 Installation
Glued connection;
Ø32 mm
Screw connection