Maintenance

The transfer switch is designed to be maintenance free under 

normal usage. However, inspection and maintenance checks 

should be made on a regular basis. Maintenance will consist 

mainly of keeping the transfer switch clean.
Visual inspections should be done at least once a month. 

Access to transfer switch must not be obstructed. Keep 

3 feet (92 cm) clearance around transfer switch. Check for 

an accumulation of dirt, moisture and/or corrosion on and 

around the enclosure, loose parts/hardware, cracks and/or 

discoloration to insulation, and damaged or discolored 

components.
Exercise the transfer switch at least once every three months 

as described in the previous section “Testing the Automatic 

Transfer Switch” unless a power outage occurs and Home 

Generator System has gone through automatic sequence. 

Allow generator to run for at least 30 minutes.
Contact a licensed electrical professional to inspect and clean 

the inside of your transfer switch at least once a year.

Specifications

UL® 1008 Listed Transfer Switch

Model 071007

Maximum Load Current:. . . . . . . . . . . . . . . . . . . . 100 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Volts
Poles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . 22,000 RMS Symmetrical Amperes*
Supervisory Contacts Rating:
  A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Volt AC
  B-B Terminals . . . . . . . . . . 1 Amp, 125 Volt AC, Pilot Duty
Weight  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 lbs.
* Short circuit rating is limited to the lowest capacity of any 

device installed.

Summary of Contents for 71007

Page 1: ...Installation Operator s Manual 100 Amp NEMA 3R Automatic Transfer Switch with AC Power Control Module Part No 202267GS Rev A 11 06 2007...

Page 2: ...dures and methods by which installation might be achieved We do not know all possible hazards and or the results of each method or procedure Save these instructions for future reference This transfer...

Page 3: ...ion 6 Unpacking 6 Mounting Guidelines 6 Power Wiring Interconnections 7 Supervisory Control Wiring 8 System Setup 9 Controls 9 Operation 9 Testing the Automatic Transfer Switch 9 Maintenance 10 Specif...

Page 4: ...ing Low voltage wire cannot be installed in same conduit as power voltage wiring Failure to follow above warning could cause personal injury damage and or malfunction of equipment warning Failure to p...

Page 5: ...n the manual Installer Responsibilities Read and observe the safety rules Read and follow the instructions given in this manual Check federal state and local codes and authority having jurisdiction fo...

Page 6: ...ting the Automatic Transfer Switch include Install the switch on a firm sturdy supporting structure The switch must be installed with minimum NEMA 3R hardware for conduit connections To prevent switch...

Page 7: ...h main distribution panel utility power and generator as shown below 1 Ensure utility power is turned OFF 2 Connect main distribution panel feeder conductors from installer supplied two pole maximum 1...

Page 8: ...er torque values Supervisory Control Wiring The supervisory control terminal strip on the control module in the transfer switch has four connections for customer use There are two sets of Normally Clo...

Page 9: ...tantly monitoring generator power If the air conditioner is called to run and there is sufficient generator power available the controller will close contacts A A to air conditioner contactor Contacts...

Page 10: ...components Exercise the transfer switch at least once every three months as described in the previous section Testing the Automatic Transfer Switch unless a power outage occurs and Home Generator Syst...

Page 11: ...l running after switch transfers to utility power Engine cool down period Engine should stop after 1 minute Generator or supervised loads air conditioner etc are operating improperly when generator is...

Page 12: ...4 J6 J5 CONTROL BOARD A A B B CT2 CT1 E2 T2 T1 E1 N2 N1 NC NO F1 F2 556 N2 N1 205 206 E2 E1 NC NO 128 127 N1 E1 TRANSFER SWITCH UTILIT Y SUPPLY 240VAC TO GENER ATOR UTILITY 240 VAC 2 AMP FUSE GENER AT...

Page 13: ...sfer Switch Wiring Diagram A A B B J1 J2 J3 J4 J6 J5 CT1 CT2 127 205 N1 N1 556 N2 128 206 E1 E1 E2 N2 CONTRO L BOARD TRANSFER SWITCH FUSE HOLDER UTILIT Y 240 VAC FROM MAIN DISTRIBUTION PANEL FROM GENE...

Page 14: ...14 BRIGGSandSTRATTON COM Transfer Switch Exploded View Parts List...

Page 15: ...NSP BAR Neutral Connection 20 B4986GS DECAL Ground 21 NSP GROUND BAR 22 SCREW Trilobular 10 32 x 3 4 23 205108GS DECAL 100A ATS 24 204433GS SPACER 25 190992GS DECAL Warning Shock 26 190984GS DECAL Fus...

Page 16: ...TIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD ABOUT YOUR WARRANTY We welcome warranty repair and apol...

Page 17: ...Manual de Instalaci n y del Operario 100 Amp NEMA 3R Conectador autom tico con AC Power Control Module...

Page 18: ...cedimientos y m todos posibles para efectuarla No conocemos todos los riesgos y o resultados posibles de cada m todo o procedimiento Guarde estas instrucciones para futuras consultas Antes de utilizar...

Page 19: ...ripci n del equipo 5 Instalaci n 6 Desempaque 6 Pautas de montaje 6 Interconexiones de cableado de energ a 7 Cableado de control de supervisi n 8 Configuraci n del sistema 9 Mandos 9 Sistema funcionam...

Page 20: ...les de suministro de energ a Si no se respeta esta indicaci n pueden producirse lesiones da os y o fallos de funcionamiento del equipo advertencia Si no hace tierra apropiadamente con un conmutador de...

Page 21: ...ilizar el conmutador de transferencia seg n se especifica en el manual Responsabilidades del instalador Lea y observe las reglas de seguridad que se encuentran en el manual Lea y siga las instruccione...

Page 22: ...e es adecuada para uso en interiores y a la intemperie Las directrices para el montaje de conectador autom tico incluyen Instale el conmutador sobre una estructura de soporte firme y resistente El int...

Page 23: ...de la caja junto a los terminales del disyuntor No utilice los orificios grandes en la parte inferior de la caja advertencia Los cables de baja tensi n no se pueden instalar en el mismo conducto que...

Page 24: ...rrectos en el interior de la caja del conectador Cableado de control de supervisi n La regleta de terminales de control de supervisi n del m dulo de control del conectador tiene cuatro conexiones para...

Page 25: ...Si se intenta activar el acondicionador de aire y la potencia del generador es suficiente el controlador cierra los contactos A A de conexi n al contactor del acondicionador de aire Los contactos B B...

Page 26: ...i n sobre la caja o a su alrededor piezas flojas grietas o p rdida de color del aislamiento y componentes da ados o descoloridos Ponga en funcionamiento el conectador al menos una vez cada tres meses...

Page 27: ...onectador transfiera la conexi n a la red p blica El per odo de enfriamiento del motor El motor deber a detenerse despu s de 1 minuto Las cargas supervisadas acondicionador de aire etc no funcionan cu...

Page 28: ...GARANT A Esperamos que disfrute de nuestra garant a y le pedimos disculpas por las molestias causadas Cualquier distribuidor de servicio autorizado puede llevar a cabo reparaciones en garant a La may...

Page 29: ...Guide d Installation et d Utilisation 100 Amp NEMA 3R Commutateur de transfert automatique avec AC Power Control Module...

Page 30: ...us informer des dangers et des risques associ s aux commutateurs de transfert et la fa on de les viter La soci t Briggs Stratton a tout fait pour fournir un groupe lectrog ne dont l installation soit...

Page 31: ...s de l Installateur 5 Description de l quipement 5 Installation 6 D ballage 6 Consignes d installation 6 Interconnexions du C blage de Alimentation 7 C blage de contr le 8 Configuration du syst me 9 C...

Page 32: ...lles et l endommagement ou le mauvais fonctionnement de l quipement avertissement Ne pas relier le commutateur de transfert la terre risque de provoquer des lectrocutions Ne touchez pas les fils d nud...

Page 33: ...indiqu dans le manuel Responsabilit s de l Installateur Vous devez lire et respecter les r gles de s curit d crites dans le manuel Vous devez lire et suivre les instructions indiqu es dans le pr sent...

Page 34: ...our usage interne et externe Consignes d installation du commutateur de transfert automatique Installation du commutateur sur une structure portante ferme et robuste Le commutateur doit tre install av...

Page 35: ...nt de l quipement Effectuez les raccords suivants entre le commutateur de transfert le panneau de distribution principal l alimentation de service et la g n ratrice tel que montr ci dessous 1 Assurez...

Page 36: ...o 14 AWG minimum 12 Serrez au couple appropri tous les raccords de fils et attaches Consultez la partie int rieure du bo tier du commutateur de transfert au sujet des couples de serrage appropri s C b...

Page 37: ...la puissance au commutateur de transfert le contr leur surveille continuellement la puissance de la g n ratrice Lorsqu une demande d activation du climatiseur est mise et que la g n ratrice a suffisa...

Page 38: ...z les accumulations de salet moisissure et ou de corrosion sur le bo tier et autour de celui ci les pi ces quincaillerie l ches les fissures et ou de la d coloration sur l isolant et les l ments endom...

Page 39: ...entation de service La p riode de refroidissement n a pas t compl t e Le moteur devrait s teindre apr s 1 minute Les charges r glables climatiseur etc ne fonctionnent pas sous l alimentation de servic...

Page 40: ...OUVEZ PROUVER LA DATE INITIALE DE L ACHAT NOUS UTILISERONS LA DATE DE FABRICATION DU PRODUIT COMME DATE DE R F RENCE POUR D TERMINER LA P RIODE DE GARANTIE PROPOS DE LA GARANTIE Nous acceptons de fair...

Reviews: