4
Series 5A and Series 5B I.S. Valve Status Monitor
Installation, Operation and Maintenance Manual
7. Hazardous Locations
The S5A and S5B I.S. (aluminum and resin trims) are
designed and certified to operate in the following
hazardous locations :
ATEX
II 1G Ex ia IIC Ga T6
II 2G Ex ia IIC Gb T6
DEMKO 18ATEX2062X
IECEx
IECEx UL 18.0073X
Ambient
1G: -25°C
≤
Ta
≤
49°C
2G: -25°C
≤
Ta
≤
65°C
Elevation 2000m max
The S5A (aluminum trim only) and S5B (aluminum
and resin trims) I.S. are also certified to operate in
the following hazardous locations :
NEC 500 Class I Division 1
Groups A, B, C, & D T6
Class II Division 1
Groups E, F, G T85°C
E202292 (UL)
NEC 505 Class I, Zone 0, AEx ia IIC T6
Class I, Zone 1, AEx ia IIC T6
CEC
Ex ia IIC Gb T6
Ambient
Zone 0: -25°C
≤
Ta
≤
49°C
Zone 1: -25°C
≤
Ta
≤
65°C
Elevation 2000m max
For cULus applications, the S5B resin housing is
only intended for use with flexible conduit.
In addition to IO&M Manual instructions, it is
required to follow all instructions specified in
Control Drawing: WD-000393.
S5A and S5B I.S. VSMs must be used in
conjunction with a third party approved
barrier that meets conditions specified in
the control drawing: WD-000393.
Enclosure may contain aluminum. Care must be
taken to avoid hazard due to impact or friction
Resin housings pose an electrostatic charging
hazard. See Control Drawing: WD-000393
Substitution of components may impair intrinsic
safety.
NOTICE
The Bray Series 5A and 5B I.S. VSMs are compliant
to the IEC/EN 60079-11 section 6.3.13 dielectric
strength requirement.
8. Pre-Installation Storage
Bray Series 5A and 5B I.S. VSMs are not weatherproof
until properly installed on the quarter-turn device
or prepared for storage. Bray cannot accept
responsibility for deterioration caused on-site once
the cover is removed.
NOTICE
Units are shipped with two screw-in plugs
(aluminum housing) or peel-off decal (resin
housing) to prevent foreign matter from
entering the unit through the conduit openings.
To prevent condensation from forming inside
these units, maintain a near constant external
temperature and store in a well-ventilated, clean,
dry room away from vibration.
Store units on a shelf or wooden pallet in order
to protect against dampness.
Keep units covered to protect against dust and
dirt.
Storage Temperature should be maintained
between -25°C and 65°C.