Series 5A and Series 5B I.S. Valve Status Monitor

Installation, Operation and Maintenance Manual

13. Position Adjustment

A single or doubled lobed cam is provided for every 
independent/main switch. Double lobed cams are 
provided when the switch configuration could 
include an auxiliary switch. Double lobed cams 
will activate both main and auxiliary switches at 
the same time.

Cams are mounted to the indicator shaft, alternating 
between red and yellow and are independently 
adjustable by hand in 3.6° increments. No special 
tools are needed for this adjustment. The self-locking 
design ensures that cams will not slip position.

The bottom red cam is intended to indicate the close 
position while the bottom yellow cam is intended 
to indicate the open position. Both of the switches 
associated with these cams are labeled accordingly. 
An additional red and yellow cam may be installed 
for most switches and can be used for mid-travel 
position indication or to provide an additional 
auxiliary open and close indication. Mid-travel 
switches are unlabeled.

Closed Travel Indication Adjustment

1.  Operate the quarter turn device until it 

reaches the desired closed position.

2.  Pull the bottom red close cam upwards 

towards the yellow cam to disengage the 
cam from the fixed cam holder.

3.  While the cam is disengaged, rotate the cam 

to the position that will activate the close 
switch. 

a.  NOTE: Do not attempt to adjust cams 

prior to disengaging the cam from the 
fixed cam holder.

4.  Release the cam and allow the locking spring 

to re-engage the cam with the fixed cam 
holder.

Open Travel Indication Adjustment

1.  Operate the quarter turn device until it 

reaches the desired open position.

2.  Push the bottom yellow open cam towards 

the bottom red cam to disengage the cam 
from the fixed cam holder.

3.  While the cam is disengaged, rotate the cam 

to the position that will activate the open 
switch. 

a.  NOTE: Do not attempt to adjust cams 

prior to disengaging the cam from the 
fixed cam holder.

4.  Release the cam and allow the locking spring 

to re-engage the cam with the fixed cam 
holder.

Mid-Travel Indication Adjustment

1.  Operate the quarter turn device until it 

reaches the desired mid-travel position.

2.  Disengage the cam from the cam holder.

a.  NOTE: Mid-travel cams are disengaged 

similarly to the open and close cams.

3.  While the cam is disengaged, rotate the cam 

to the position that will activate the mid-
travel switch. 

a.  NOTE: Do not attempt to adjust cams 

prior to disengaging the cam from the 
fixed cam holder.

4.  Release the cam and allow the locking spring 

to re-engage the cam with the fixed cam 
holder.

Summary of Contents for 5A Series

Page 1: ...SERIES 5A AND 5B INTRINSICALLY SAFE VALVE STATUS MONITOR Installation Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY BRAY COM...

Page 2: ......

Page 3: ...n 3 7 Hazardous Locations 4 8 Pre Installation Storage 4 9 Mounting 5 9 1 Adjustable Bracket 5 9 2 Fixed Bracket 6 10 Accessing Internal Components 7 10 1 Cover Removal 7 10 2 Cover Installation 7 11...

Page 4: ...this device is installed must have proper safeguards to prevent injury to personnel or damage to equipment should failure of system components occur 3 Qualified Personnel A qualified person in terms o...

Page 5: ...and 5B Intrinsically Safe Valve Status Monitors VSMs provide visual and electrical indication of position of any VDI VDE 3845 compliant quarter turn device The S5A and S5B I S VSMs are designed to op...

Page 6: ...with a third party approved barrier that meets conditions specified in the control drawing WD 000393 Enclosure may contain aluminum Care must be taken to avoid hazard due to impact or friction Resin h...

Page 7: ...bottom of the VSM 5 Attach mounting bracket and nylon washers to the VSM using mounting bracket bolts a Tighten mounting bolts in a cross pattern to 70 8 in lbs 8Nm b Ensure that the bracket remains...

Page 8: ...M shaft engages with actuator pinion 3 Install bracket mounting bolts with lock washers as seen below a Tighten mounting bracket bolts to 44 3 in lbs 5Nm 9 2 2 Resin Brackets Bray s single piece resin...

Page 9: ...y new holes in the enclosure Do not remove the screw in conduit plugs aluminum housing or peel off decal resin housing until it is time to wire into the unit s terminal blocks Do not tamper with or mo...

Page 10: ...olts in a cross pattern to 80 lb in 9 Nm for aluminum housing or 17 7 lb in 2 Nm for resin housing Reference Cover Installation NOTICE If the valve status monitor is mounted on a vertical pipe it is r...

Page 11: ...cations when making modifications to the assembly NOTICE Ensure that open and close cams are properly set after any modification to visual indication Bray Series 5A and 5B I S VSM visual indication ca...

Page 12: ...s towards the yellow cam to disengage the cam from the fixed cam holder 3 While the cam is disengaged rotate the cam to the position that will activate the close switch a NOTE Do not attempt to adjust...

Page 13: ...nal is received in close position or vice versa Field wiring is reversed Rewire field wiring Corrosion inside unit Condensation forming Seal conduit opening Water leaking in Check all seals and possib...

Page 14: ...12 Series 5A and Series 5B I S Valve Status Monitor Installation Operation and Maintenance Manual 15 Exploded Views 1 2 3 4 5 7 6 Exploded View 5A Aluminum Trim...

Page 15: ...13 Series 5A and Series 5B I S Valve Status Monitor Installation Operation and Maintenance Manual Exploded View 5A Resin Trim 6 3 5...

Page 16: ...14 Series 5A and Series 5B I S Valve Status Monitor Installation Operation and Maintenance Manual 1 2 3 4 5 7 6 Exploded View 5B Aluminum Trim...

Page 17: ...15 Series 5A and Series 5B I S Valve Status Monitor Installation Operation and Maintenance Manual Exploded View 5B Resin Trim 1 6 2 4 5 3...

Page 18: ...Resin 16 Replacement Parts 16 2 Replacement Parts Resin Housing 16 1 Replacement Parts Aluminum Housing 17 Basic Tools Common To All Units Terminal Connections Screwdriver tip flat blade All switches...

Page 19: ...17 Series 5A and Series 5B I S Valve Status Monitor Installation Operation and Maintenance Manual...

Page 20: ...Texas 77041 Tel 281 894 5454 bray com THE HIGH PERFORMANCE COMPANY BRAY INTERNATIONAL PRIMARY SALES AND SERVICE LOCATIONS USA Houston Texas CHINA Hangzhou Zhejiang MEXICO Zapopan Jalisco RUSSIA Moscow...

Reviews: