19
Manual C118 EN Rev04
04.2017
18
Automatic Power Shut-Off
To save battery capacity, the C118 can be automatically
shut off, when idling for 10 min.
Step 08 enables this function by its parameter:
0 = function disabled
1 = function enabled
Step No. 08
Automatic Switch
Power Off
Input Frequency Pre-Divider
This facility is very helpful whenever several pulses per
revolution (or other period) with unequal distance must be
evaluated. For instance, screw heads on the rotating object
placed at unequal angular positions. Piston and oval gear
flowmeters may show unequal pulse spacing over one revo-
lution, too.
Setting the parameter of this step to the number of pulses
included into one revolution, the function will divide the
incoming pulse rate accordingly. This returns the pulse se-
quence to one pulse per revolution, what obviously ensures
the most accurate repetition, as the best basis for stable
measurements. Setting range 001 …255. Any higher num-
ber will be rejected.
For pulse to pulse measurements (to trace variations in the
angular speed), or at very low speed (to avoid an early shut-
off by the maximum measuring time), leave the parameter
at 001.
Note:
All adjustments refer to the divided input frequency.
The pulse output repeats the divided input frequency.
Step No. 09
Input frequency
Divider
Decimals in Totalizing Mode SF
If the count step width in totalizing is a fraction of the re-
quested quantity unit, as given by the application and/or the
computing factor, a decimal point can be set into the dis-
play. Follow the procedure as described for Step No. 05.
Step No. 10
Decimals in
Total Readings
Manual C118 EN Rev04
04.2017
19
Parameters set on delivery (default values)
Step No.
Function
Value
00
Minimum Time Allowance
0.50 s
01
Maximum Time Allowance
8.00 s
02
Computing Factor Mode
0 (multiplying)
03
decimals
------. (none)
04
numerical 000001
05
Display decimals
------. (none)
06
Analog Output
high end
010000
07
low end
000000
08
Automatic Power off
1 (active)
09
Input Pre-Divider
001
10
Decimals in SF Display
------. (none)