POWER CONNECTION

To avoid possible electrical shock, be sure the electrical current is turned off at the main switch 

prior to wiring or servicing of unit.

1. Remove the access panel, by removing four screws, two on the front and two on the back.

2. Remove desired knockout on side or back of the heater.

3. Following the correct unit wiring diagram, connect the power supply and electrical ground to the

    correct terminals using accepted practices recognized by local codes.  See Table 1 for minimum

    circuit requirements. 

            

4. Replace the access panel, tighten the screws to ensure a good seal to help prevent dust and dirt

    from entering the control compartment.

0"

24"

MINIMUM

DISTANCE

FROM

FRONT

TO ANY

OBJECT

MINIMUM INSTALLATION CLEARANCES:

SIDES, TOP AND BOTTOM  0 INCHES

REAR:   8 INCHES  (203mm)

FRONT:  24 INCHES  (610mm)

Dégagements minimums MONTAGE:

Côtés, le haut et le bas 0 pouces

ARRIÈRE: 8 pouces (203mm)

AVANT: 24 pouces (610mm)