REV. LEVEL ECO 1-7521 03/2019 FORM 8208
3 OF 5
Fig. 2
POWER CONNECTION
To avoid possible electrical shock, be sure the electrical current is turned off at the main switch
prior to wiring or servicing of unit.
1. Remove the access panel, by removing four screws, two on the front and two on the back.
2. Remove desired knockout on side or back of the heater.
3. Following the correct unit wiring diagram, connect the power supply and electrical ground to the
correct terminals using accepted practices recognized by local codes. See Table 1 for minimum
circuit requirements.
4. Replace the access panel, tighten the screws to ensure a good seal to help prevent dust and dirt
from entering the control compartment.
0"
24"
MINIMUM
DISTANCE
FROM
FRONT
TO ANY
OBJECT
MINIMUM INSTALLATION CLEARANCES:
SIDES, TOP AND BOTTOM 0 INCHES
REAR: 8 INCHES (203mm)
FRONT: 24 INCHES (610mm)
Dégagements minimums MONTAGE:
Côtés, le haut et le bas 0 pouces
ARRIÈRE: 8 pouces (203mm)
AVANT: 24 pouces (610mm)
14.4
14.6
5.1
8.0"
MIN. TO WALL
10.0
W
A
L
L
FLOOR
0"