REV. LEVEL ECO 1-7521 03/2019 FORM 8208
5 OF 5
MAINTENANCE
:
Caution: Make certain that the power source is disconnected before attempting to service or disassemble
any component. If the power disconnect is out of the line of sight, lock it in the OPEN position and tag to
prevent the application of power.
Electrical
:
Once a year inspect the control panel wiring to make certain insulation is intact and all connections both
factory and field are tight. Inspect all heater and relay contacts. If the contacts appear badly pitted or
burned, replace the contactor/relay.
Cleaning
:
Clean the unit casing, fan and motor once a year. A dirty motor will tend to run hot and eventually will
be damaged internally. Any rust spots on the casing should be cleaned and repainted. The element
can be cleaned by removing the outer cabinet. Do not use any liquid to clean electric components.
Lubrication
:
All units have fan motors that are permanently lubricated. No oiling is required.
425 Hanley Industrial Court St. Louis, Missouri 63144
1-888-731-7010
www.braschmfg.com [email protected]
WIRING DIAGRAMS
BH-P-961-U5000K-T
BH-P-961-U5000U-T
L3
L2
L1
LTB
CONTACTOR
COIL
CTB
LIMIT CONTROL
DELAY
FAN
CONTROL TRANSFORMER
ELEMENT
T-STAT
240V 3ph
AWGA MPS
USE COPPER
CONDUCTORS
ONLY
14
12
12
16
10
24
83
6
CAUTION: USE SUPPLY WIRES SUITABLE FOR
AT LEAST 90°C (194°F)
ATTENTION: UTILISEZ DES FILS
D'APPROVISIONNEMENT APRÈS AU MOINS 90 ° C
(194 ° F)
LTB
CAUTION: USE SUPPLY WIRES SUITABLE FOR
AT LEAST 90°C (194°F)
ATTENTION: UTILISEZ DES FILS
D'APPROVISIONNEMENT APRÈS AU MOINS 90 ° C
(194 ° F)
36
8
24
10
16
12
12
14
USE COPPER
CONDUCTORS
ONLY
AMPS
AWG
480V 3ph
CONTACTOR
COIL
CTB
FAN
DELAY
LIMIT CONTROL
CONTROL TRANSFORMER
L3
L2
L1
ELEMENT
THERMOSTAT
M