MAINTENANCE

:

Caution: Make certain that the power source is disconnected before attempting to service or disassemble 

any component.  If the power disconnect is out of the line of sight, lock it in the OPEN position and tag to 

prevent the application of power.

Electrical

:

Once a year inspect the control panel wiring to make certain insulation is intact and all connections both 

factory and field are tight. Inspect all heater and relay contacts. If the contacts appear badly pitted or 

burned, replace the contactor/relay.

Cleaning

:

Clean the unit casing, fan and motor once a year.  A dirty motor will tend to run hot and eventually will 

be damaged internally.  Any rust spots on the casing should be cleaned and repainted.  The element 

can be cleaned by removing the outer cabinet. Do not use any liquid to clean electric components.

Lubrication

:

All units have fan motors that are permanently lubricated. No oiling is required.

425 Hanley Industrial Court   St. Louis, Missouri 63144

1-888-731-7010

  www.braschmfg.com      [email protected]

WIRING DIAGRAMS

BH-P-961-U5000K-T

BH-P-961-U5000U-T

L3

L2

L1

LTB

CONTACTOR

COIL

CTB

LIMIT CONTROL

DELAY

FAN

CONTROL TRANSFORMER

ELEMENT

T-STAT

240V 3ph

AWGA MPS

USE COPPER

CONDUCTORS

ONLY

14

12

12

16

10

24

83

6

CAUTION: USE SUPPLY  WIRES SUITABLE FOR

AT LEAST 90°C (194°F)

ATTENTION: UTILISEZ DES FILS

D'APPROVISIONNEMENT APRÈS AU MOINS 90 ° C

(194 ° F)

LTB

CAUTION: USE SUPPLY  WIRES SUITABLE FOR

AT LEAST 90°C (194°F)

ATTENTION: UTILISEZ DES FILS

D'APPROVISIONNEMENT APRÈS AU MOINS 90 ° C

(194 ° F)

36

8

24

10

16

12

12

14

USE COPPER

CONDUCTORS

ONLY

AMPS

AWG

480V 3ph

CONTACTOR

COIL

CTB

FAN

DELAY

LIMIT CONTROL

CONTROL TRANSFORMER

L3

L2

L1

ELEMENT

THERMOSTAT

M