background image

B - C r e a m   &   B - c r e a m   H D

44

ENGLISH

12. 4  HOW TO CHARGE THE MACHINE WITH GAS

The “pressure gauge” shown in figure 5 is the type with 4 filling units (and 4 valves) because this type is most widely available on the 
market, and it allows charging with gas both through the “High” and “Low Pressure” zones of the refrigerator circuit.

The refrigerator circuit on our machines is built so that the charging of gas may only be carried out through the compressor charging 
tube ("Low Pressure" area): for this reason, the “HI” filling unit is not mentioned or used in our procedures and the “HI” valve should 
therefore remain closed at all times.

1

Verify how many grams of gas should be decanted. This data, along with the type of gas, is indicated on the machine's

information plate.

2

Remove any containers and mixers from the machine.

3

Connect the machine’s plug to a power supply and switch the master switch to the "I" position.

4

Switch all the “Mixer and Refrigeration” switches to the “I” position and wait until all electrovalves are open (only in multiple

machines) and the compressor starts up.

5

Open the valve on the charging unit.

6

Open the “REF” valve on the pressure gauge slowly and gently, so that the refrigerant is pushed into the circuit in gas form.

7

When the quantity of gas indicated on the Information Plate has been decanted, the refrigerator circuit is charged. Close the

“REF” valve and the valve on the charging unit, keeping the compressor running for a further few minutes.

8

Make sure that all the evaporator cylinders are covered with frost.

9

Close the “LOW” valve, disconnect the “LOW” pipe from the compressor charging pipe and screw the cap onto the bottom of the

charging pipe.

As an indication, the temperatures and corresponding evaporation and condensation pressures at which the machines must operate 
are indicated below.

These temperatures and pressures must be verified under the following operating conditions:

Ambient temperature: 32 °C

Temperature produced in the tank: 0 °C

In these conditions, the evaporation temperature should be approximately -10 °C and the condensation temperature approximately 
50°C.

These temperatures should correspond with the temperatures indicated in the table below, depending on the refrigerant gas used:

13  COMPRESSOR FAULTS

To establish if a malfunction has occurred, proceed as follows:

1

Disconnect the machine’s plug from the power supply.

2

Disconnect the conductors from the compressor terminals.

3

Using an ohmmeter, measure the isolation between the terminals and the compressor housing. If the instrument indicates

continuity, the compressor has short-circuited.

4

In this situation, the compressor must be replaced using the following method:

5

Collect the gas as described in the paragraph "Discharging the gas".

6

Remove the faulty compressor.

7

Eliminate the cause of the compressor fault (check the conditions of the condenser both when the machine is started up and

when it is operating, and also the condition of the starter relay as possible sources and causes of the fault).

8

Install a new compressor and a new dehydrator filter.

9

Empty and charge the circuit as described above.

Refrigerant gas

Evaporation Pressure 

Condensation Pressure

R134a

1,00 bar

12,00 bar

R404a

3,20 bar

22,00 bar

Summary of Contents for B-cream HD 1

Page 1: ...d 16 and the power supply transformer 15 for both the circuit boards and the geared motor to drive the mixers The upper half of the dispenser contains the transparent tank 8 designed for the food prod...

Page 2: ...ned off If you press it for two seconds the dispenser switches to Cleaning mode the mixer is on but the cooling is off F Conservation indicator light flashing light product conservation mode selected...

Page 3: ...selected product ready H Ice cream production key allows you to select the ice cream production operating mode On dispensers with more than one tank if you hold this key down while the tank is in ice...

Page 4: ...torage mode PA05 parameter As well as the operating modes described in the Instruction Manual the dispenser may be started up in other modes which can be used for technical support These modes are sum...

Page 5: ...functioning correctly Master switch key H IMPORTANT On dispensers with more than one tank the operating parameters from PA01 to PA10 must be set separately for each tank NAME DESCRIPTION ADJUSTMENT IN...

Page 6: ...in more containers from the factory parameters PA11 to PA 27 are common to all the distributor and therefore can only be adjusted by the control panel on the right container NAME DESCRIPTION ADJUSTME...

Page 7: ...w to verify is the efficiency of the cooling system which can be reduced for example due to a leak of refrigerant gas In order to execute such a check a test with product 90 minutes long is required 7...

Page 8: ...is operating in Service Mode Service Mode or Super AL09 Error Hall probes This alarm stops the operation of the machine AL10 Lack of communication between master and slave card 1 This alarm stops the...

Page 9: ...r filter 2 Loosen the fastening screws and remove the side panels 3 Loosen the screws and remove the front panel Then remove the condensation water drain cover 4 Once you have removed the cover the ta...

Page 10: ...he rear of the board Loosen all the housing securing screws and then remove the board itself 3 To remove the power board you need to disconnect all the connectors then pull down the two side anchor ta...

Page 11: ...EFROSTING FAN AND THE LID PRESENCE SENSORS 1 Remove the air conveyor by pressing on either side Pull the defrosting fan out of its seat in the conveyor The lid presence detectors are situated at the r...

Page 12: ...To update the control board firmware perform the steps described below 1 Collect the programmer to the USB port on the PC where the firmware update files are stored The programmer will be recognised b...

Page 13: ...GRAMMING light will flash for a few seconds and when it remains permanently lit programming has been terminated correctly 4 Switch off the master switch and disconnect the machine from the mains 5 Dis...

Page 14: ...ure 4 Referring to figure 3 proceed as follows 1 Begin the inspection at the High Pressure zone discharge of the compressor Check around the seals 2 Follow the copper pipes to the condenser and check...

Page 15: ...illing unit on the pressure gauge to the charging unit 2 Connect the VAC filling unit to the vacuum pump and open the VAC valve 3 Open the valve on the charging unit and for a moment also open the REF...

Page 16: ...re covered with frost 9 Close the LOW valve disconnect the LOW pipe from the compressor charging pipe and screw the cap onto the bottom of the charging pipe As an indication the temperatures and corre...

Page 17: ...ply circuit board 2 Transformer 9 Display circuit board 3 Electrovalve 10 Temperature probe 4 Compressor 11 Reed safety switches 5 Fan 13 LED board hat optional 6 Geared motor 14 LED Board cop shoulde...

Page 18: ...board 2 Transformer 10 Temperature probe 3 Electrovalve 11 Reed safety switches 4 Compressor 13 LED board hat optional 5 Fan 14 LED Board cop shoulder optional 6 Geared motor 15 LED Strip cop shoulder...

Page 19: ...DIAGRAM POWER SUPPLY DISPLAY MINIGEL 17 TOPOGRAFIC DIAGRAM POWER SUPPLY DISPLAY MINIGEL PLUS KEY M1 Temperature probe M2 MASTER board M3 Faucet Reed switch opt KEY M1 Temperature probe M2 MASTER board...

Page 20: ...ost fan M4 Solenoid valve M12 Earthing M5 Compressor M13 Slave 1 board M6 Display board M14 Slave 2 board M7 Not connected M15 Closed machine without solenoid valve M8 Top cover LED board M16 Open mac...

Page 21: ...49 20 TOP COVER LED TOPOGRAPHY 21 REAR COVER LED TOPOGRAPHY KEY M1 Motherboard M2 LED strip power supply board KEY M1 LED power supply board M2 Rear cover LED strip...

Page 22: ...e density adjustment will be auto matically reduced by one unit Hold down the H key for two seconds to cle ar the alarm message The machine does not start up Message AL04 is indicated on the display T...

Page 23: ...ine to the power supply Message AL13 shown on the display System clock out of order The machine can work but the defrost timer can t be used Replace display pcb Message AL14 shown on the display Batte...

Page 24: ...otor is not functioning short circuit or mechanical blockage Replace the compressor see chapter 10 Electrovalve is not opening coil Replace electrovalve coil Electrovalve is not opening body Replace e...

Reviews: