WARNING
!
16
LS3
Series
Suspension of the heater must conform to applicable codes referenced in the Safety section and
these instructions.
1
Lay all radiant tubing out in the following order. Position tubes in approximate location (see Figure 3.4).
• 10 ft. 4” to 3” O.D. titanium treated combustion chamber.
• 3” O.D. aluminized radiant emitter tube(s) if applicable.
2
Connect the female end of the titanium combustion chamber to the 16” burner tube by
using the 4” stainless steel tube clamp (TP-220).
Important!
The 10 ft. tianium alloy treated combustion chamber must be placed as the first tube
downstream of the burner control box. The combustion chamber has a yellow identification label
located on the tube.
3
Place a 4” tube hanger (TP-19B) on the tapered titanium combustion chamber’s 4” O.D. end. The
spacing between the burner control box mounting brackets and the 4” tube hanger should be 2’-4”.
4
Mark locations for hanging points.
NOTE:
If the available hanging points do not allow for the recommended spacing then additional
hangers (P/N: TP-19B (4”) or TP-1079(3”)) may be necessary.
• The spacing between the burner control box mounting brackets and the first hanger should be
approximately 2’-4”.
• The space between the first two hangers placed on the first tube, should be approximately 8’-10”.
• The space between hangers thereafter, one per tube, should be approximately 9’-8”.
Hanger Placement and Suspension
Improper suspension of the tube heater may result in collapse and being crushed. Always
suspend from a permanent part of the building structure that can evenly support the total
force and weight of the heater.
Failure to maintain minimum clearance to combustibles may result in fire and/or explosion,
property damage, serious injury or death. Always maintain minimum clearances and post
clearance safety limit signs or the clearance safety tag where needed.
3.0
Installation •
Hanger Placement and Suspension