Logic Low: -10V minimum, 0.8V maximum.
2V minimum, 10V maximum.
Logic High:
Remote reset, remote lockout.
Functions:
Output 1 / Output 2
Relay Rating: 2A/240 VAC, life cycles 200,000 for resistive load.
Source Voltage 5V, current limiting resistance
Pulsed Voltage:
66 ohms.
Triac (SSR) Output
1A/240 VAC
Rating:
20A for 1 cycle
Inrush Current:
50 mA rms
Min. Load Current:
3 mA rms
Max. Off-state Leakage:
1.5 V rms
Max. On-state Voltage:
1000 Mohms min. at 500 VDC
Insulation Resistance:
2500 VAC for 1 minute
Dielectric Strength:
DC Voltage Supply Characteristics ( Installed at Output 2 )
Type Tolerance Max. Output
Current
Ripple
Voltage
Isolation
Barrier
20 V
A
V
1
25 mA
0.2 Vp-p
500 VAC
500 VAC
500 VAC
12 V
A
0.6 V
40 mA
0.1 Vp-p
5 V
A
0.25 V
80 mA
0.05 Vp-p
Data Communication
Interface : RS-485 ( up to 247 units )
Modbus Protocol RTU mode
Protocol :
1 - 247
Address :
0.3 ~ 38.4 Kbits/sec
Baud Rate :
8 bits
Data Bits :
None, Even or Odd
Parity Bit :
1 or 2 bits
Stop Bit :
50 bytes
Communication Buffer :
Event Input
50