TROUBLESHOOTING
cont.
Symptom:
LO
is shown in the thermostat display where the room temperature is normally displayed.
Potential Solutions:
The temperature sensed by the thermostat is lower than the 40˚ F (5˚ C) lower limit of the
thermostat’s display range. The display will return to normal after the sensed temperature rises within the 40˚ to 99˚ F
(5˚ to 37˚ C) display range. If the temperature in the controlled space seems to be normal, wait for the thermostat to
acclimate to the correct room temperature. If the room seems to be colder than usual, turn on the heating system to
raise the temperature as needed for comfort within the room.
This condition could occur from the system being turned off during a cold weather period or upon installation when
the thermostat has been stored for a long period of time in a cold vehicle or location prior to being installed. The
thermostat should be allowed to warm up prior to installation in order to provide proper heating control once installed.
Symptom:
Fan continues to run all the time whether the system is on or off.
Potential Solution:
Verify that the fan is programmed to run in
AUTO
mode. This will allow the fan to run only
when the heating or cooling system is turned on and running.
Check thermostat wiring to make sure that the fan control wiring is connected to the correct terminals on the
wiring terminal block (see section 6 of the Installer Guide).
Symptom:
Unit will not enter program mode.
Potential Solution:
Non-Programmable mode was selected during Installer Setup (see section 4 of the Installer Guide).
Symptom:
Air conditioning stays on after set point is reached.
Potential Solution:
Dehumidification control is enabled (see section 3.17).
Symptom:
Temporary override of the program set point is limited.
Potential Solution:
Override limit was set in user options (see section 2.4.7).
Symptom:
Heating or cooling set point cannot be raised above a certain limit.
Potential Solution:
Set point limit was set in installer options.
Symptom:
Heating or cooling system turns on ahead of scheduled program times.
Potential Solution:
Adaptive recovery mode was enabled in installer options.
5
YEAR
WARRANTY
LIMITED
Store this
booklet for
future reference
©2008 Braeburn Systems LLC • Patents Pending • All Rights Reserved. Pub. No. 5400-110-001
Braeburn Systems LLC warrants each new Braeburn thermostat against any defects that are
due to faulty material or workmanship for a period of five years after the original date of
purchase by a professional service technician. This warranty and our liability does not apply to
batteries, nor does it include damage to merchandise or the thermostat resulting from
accident, alteration, neglect, misuse, improper installation or any other failure to follow
Braeburn installation and operating instructions.
Braeburn Systems LLC agrees to repair or replace at its option any Braeburn thermostat
under warranty provided it is returned postage prepaid to our warranty facility in a padded
carton within the warranty period, with proof of the original date of purchase and a brief
description of the malfunction. This limited warranty does not include the cost of removal or
re-installation.
This warranty gives you specific legal rights and you may also have other rights that vary from
state to state or province to province. Answers to any questions regarding our limited warranty
may be obtained by writing our corporate offices.
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S. Only)
630-844-1968 (Outside the U.S.)
WARRANTY FACILITY:
Braeburn Systems LLC
Attn: Warranty Department
2215 Cornell Avenue
Montgomery, IL 60538