background image

24

3

ADDITIONAL 

OPERATION FEATURES

cont.

3.17

  

Humidification and Dehumidification 

(continued)

If both humidification and dehumidification control are not enabled, 
the current room humidity level can still be displayed by pressing 
the 

PROG

 and 

DAY/TIME

 buttons at the same time. The unit will 

return to the normal mode in 15 seconds.

NOTE:

  

If Automatic Humidity Limiting was enabled in the installer 

options, the humidification set point may be automatically adjusted 

to compensate for changes in outdoor temperatures.

3.18

  Low Battery Detection and Replacement

This thermostat requires two (2) properly installed “AA” Alkaline 
batteries to maintain the system clock and to provide power for 
the thermostat if 24 volt AC power is not connected to the terminal 
block. This thermostat is equipped with a low battery detection 
feature that constantly monitors the batteries during normal 
operating mode to determine whether they have sufficient power 
to provide proper operation. When this feature determines that the 
battery status is low, a solid low battery indicator will appear in the 
display for 30 days. It is recommended that the batteries be replaced
immediately to maintain system operation and / or clock settings. 
If the battery continues to be low, the indicator will flash every 2 seconds for 30 days. After 30 days the battery 
indicator will start to flash every 1 second until the batteries are replaced. 

Replacing the Batteries

1.

  Open the front cover and locate the battery compartment door.

2.

  Gently remove the two “AA” Alkaline batteries located in the battery compartment.

3.

  Install two new “AA” Alkaline batteries into battery compartment. Make sure to match the positive (+) ends of    

  the batteries with the positive (+) terminals located in the battery compartment.

4.

  Close battery compartment and verify that the low battery indicator does not appear in the display.

25

4

 

TROUBLESHOOTING

®

Symptom:  

Fan continues to run in cooling mode when the system has turned off.

Potential Solution:  

The Residual Cooling Fan Control Feature can allow up to a 90 second fan delay after cooling 

system shutdown for energy efficiency gains. The default setting is 60 seconds. This can be changed to disable this 
feature or shorten the time period if desired (see section 4 of the Installer Guide).

Symptom:

  

Thermostat does not turn on heating or cooling system.

Potential Solution:

  Check to see if 

OFF

 is shown in display. This indicates that the system is turned off at the 

thermostat. Press the system button to select 

HEAT

 or 

COOL

 mode. After the compressor short cycle protection period 

expires the system should start within several seconds.
Compressor protection features may be in effect due to compressor short cycle conditions, power outages or rolling 
blackouts. See section 3.15 for full explanation of this feature.

Heat pump may be malfunctioning. Look in the lower left corner of the thermostat display. If the word 

CHECK

 is present, 

call a professional service technician to confirm heat pump operation and provide necessary service. If heating is 
required, you can press the system button to 

EMER

 setting, which may start the Emergency Heat source to provide 

heating until the heat pump can be serviced.

Symptom:

  

Thermostat turns on heating instead of cooling, or cooling instead of heating.

Potential Solution:

  Check thermostat wiring to make sure that the heating and cooling stages are connected to the 

correct terminals on the wiring terminal block (see Installer Guide, section 6).

Symptom:

  

Fan runs intermittently or when system is off.

Potential Solution:

  This is normal operation when fan switch is in recirculate (      ) mode.

Symptom:

  

System turns on prior to the end of a setback period.

Potential Solution:  

Thermostat is in Adaptive Recovery Mode (see section 3.11).

 

Symptom:  

Thermostat turns heating or cooling system on too often or not often enough.

Potential Solution:  

Increase or decrease first stage temperature differential setting as appropriate to provide the 

desired performance level (see section 2.4).

 

Summary of Contents for Premier 5400

Page 1: ...e timer and recirculating fan to default settings Button Turns on backlight for 10 seconds Button Increases setting time temperature etc Scrolls between option settings Button Decreases setting time temperature etc Scrolls between option settings 1 1 2 3 4 5 6 7 9 10 model 5400 shown with cover open 8 9 7 1 6 2 3 4 5 10 MODEL 5400 2008 Braeburn Systems LLC Patents Pending All Rights Reserved Pub N...

Page 2: ...SET 2 2 PROGRAMMING USER SETTINGS 2 3 Setting Thermostat System Selection The system can be selected by pressing the System button There are five possible settings to select from AUTO COOL OFF HEAT and EMER AUTO Auto can only be selected if it was enabled by the installer see Section 4 of the Installer Guide If AUTO is selected the system cycles between heating and cooling as determined by the set...

Page 3: ...n again and the LCD display will show d3 SET X where X equals the F C differential setting This is the current third stage differential setting 6 Press the or button to set the third stage differential to your desired setting of 1 2 3 4 5 or 6 F 0 5 1 0 1 5 2 0 2 5 or 3 0 C 4 2 PROGRAMMING USER SETTINGS cont 5 2 4 2 Setting the Filter Check Monitor see also section 3 7 The default setting is 0 day...

Page 4: ...e X is the temporary override limits 18 Press the or button to change the Temporary Override Time Limit to the desired value of 4 3 2 or 1 hour 2 4 8 Setting the Multi Level Keypad Lockout Code see section 3 10 19 Press and hold the RETURN button for four seconds Press RETURN button repeatedly until 000 SET LOCK is displayed 20 Press the or button to enter a 3 digit code using the RETURN button to...

Page 5: ...mming mode was selected during the Installer Setup Installer Guide the default program is the 2 events per day shown in the chart above Weekday Weekend MORN DAY EVE NIGHT Time 6 00 pm Heat 70 F 21 C Cool 75 F 24 C Time 8 00 am Heat 62 F 17 C Cool 83 F 28 C Time 6 00 am Heat 70 F 21 C Cool 75 F 24 C Time 10 00 pm Heat 62 F 17 C Cool 78 F 26 C 4 Event Time 6 00 pm Heat 70 F 21 C Cool 75 F 24 C Time ...

Page 6: ...le in auto changeover mode When you place the system in the HEAT or COOL modes of operation an appropriate indicator will appear in the LCD display when the system is running When you place the system in the OFF mode the display will indicate OFF NOTE If the PROG button is pressed while AUTO is selected the thermostat will switch from the AUTO mode to the mode currently in the display NOTE If Auto...

Page 7: ...utomatically 2 PROGRAMMING USER SETTINGS Entering Your Program 7 DAY Commercial Mode 1 Press the PROG button to enter the Program setting mode Press the SYSTEM button to select HEAT to set heating times and temperatures OCC occupied set point of the Whole Week will be displayed The display will show M TU W TH F SA SU to indicate the whole week is being programmed The hour portion of the set point ...

Page 8: ...r portion of the set point time and the AM PM indicator will be flashing 6 Follow steps 3 through 5 to set the set point times temperatures and fan mode for the periods of DAY EVE and NIGHT 2 PROGRAMMING USER SETTINGS cont 15 Entering Your Program 5 2 DAY Residential Mode continued 7 After pressing the PROG button you will enter the Weekend Program Group The display will show SA SU to indicate the...

Page 9: ...talled at setup the display temperature is either the temperature at the sensor or an average of the temperature at the sensor and the temperature at the thermostat 17 cont 3 ADDITIONAL OPERATION FEATURES 3 4 Remote Outdoor Sensor if installed The Braeburn Remote Outdoor Sensor is used for determining if balance points have been exceeded humidity control and for outdoor temperature display It is n...

Page 10: ...y See instructions provided with your UV source for recommendations on interval setting When the selected interval has been reached and required replacement has been performed press the RETURN button in any normal mode to reset the timer and turn off the warning 19 3 ADDITIONAL OPERATION FEATURES cont 3 9 Humidifier Pad Monitor see section 2 4 4 for setting The Humidifier Pad Monitor displays a re...

Page 11: ... used The proper operation of this function is preprogrammed into this thermostat No user changes are necessary 20 3 ADDITIONAL OPERATION FEATURES cont 3 11 Adaptive Recovery Mode ARM In order to maximize comfort and energy efficiency this thermostat is equipped with Adaptive Recovery Mode ARM This feature minimizes the amount of time required by the heating or cooling system to reach the new set ...

Page 12: ... Limits limit how much the thermostat can be adjusted from the program set points when the thermostat is used in the programmable mode This will not allow the user to set a temporary override in the heat or cool mode past the limit from the program set points The Temporary Override Adjustment Limits can only be used in the non programmable mode when the security level is at level 1 This will not a...

Page 13: ...m Fan continues to run in cooling mode when the system has turned off Potential Solution The Residual Cooling Fan Control Feature can allow up to a 90 second fan delay after cooling system shutdown for energy efficiency gains The default setting is 60 seconds This can be changed to disable this feature or shorten the time period if desired see section 4 of the Installer Guide Symptom Thermostat do...

Page 14: ...digit press the RETURN key for 1 second The display will return to the normal mode If an incorrect code is entered the display will flash no Symptom Keypad does not function Potential Solution Keypad is locked check for LOCK segment in display Symptom Thermostat will not follow program set points Potential Solutions Check current time of day day of week program settings Verify AM PM indicator is a...

Page 15: ... set point is limited Potential Solution Override limit was set in user options see section 2 4 7 Symptom Heating or cooling set point cannot be raised above a certain limit Potential Solution Set point limit was set in installer options Symptom Heating or cooling system turns on ahead of scheduled program times Potential Solution Adaptive recovery mode was enabled in installer options 5YEAR WARRA...

Reviews: