background image

S59-4016 Series 

Installation

4

 

3/30/2017

 Bradley 

• 215-1710 Rev. E; ECN 17-09-007

IMPORTANT!  Before attempting to troubleshoot the valve or disassemble the components, check for the 

following conditions:
•  If stop valves are used, make sure that they are fully open.
•  Make sure that the hot and cold inlet pipes are connected properly, and that there are no cross-

connections or leaking stop valves.

•  Check the hot water heater output to make sure that it is at least 10° F above the set 

temperature.

Thermostatic Mixing Valve Troubleshooting

Close the appropriate shut-off valves prior to disassembly and 

reopen the valves after inspection and repair is complete.

Problem

Cause

Solution

External leaks.

Damaged cartridge or O-rings .

Replace cartridge with part number 269-2000S

Improper water 

temperature or 

temperature 

fluctuation.

Hot water supply is not 10° above 

desired set point .

Increase hot water supply temperature

Valve temperature is not properly set .

Adjust the temperature as shown on page 2 step 2 .

Limited water 

flow.

Dirt and debris have built up in the 

valve or strainer .

1 .  Check to make sure both hot and cold supplies are connected to the Navigator 

mixing valve and that they have water flow .

2 .  Remove cover and U-clip . Remove the cartridge and clean the strainer . It is not 

required to grease cartridge, however if desired, use silicone grease only . Do 

not use grease on check valves .

 

Summary of Contents for Navigator S59-4016 Series

Page 1: ...6X PEX Connections S59 4016N NPT Connections S59 4016S Sweat Connections S59 4016Y PEX Connections Table of Contents Supplies and Tools Required 3 Installation 3 Maintenance and Troubleshooting 4 Assembly of Components and Parts List 5 Temperature Range 59 140 F Maximum Pressure 125 PSIG Inlet Temperature Hot 120 180 F Inlet Temperature Cold 33 80 F Minimum Temperature Differential from valve set ...

Page 2: ...maximum life and proper product function Periodic Inspection and Yearly Maintenance by a licensed contractor is required Corrosive water conditions and or unauthorized adjustments or repairs could render the valve ineffective for its intended service Frequency of cleaning and inspection depends upon local water conditions IMPORTANT Read this entire installation manual to ensure proper installation...

Page 3: ...1 Connect Supply Lines DO NOT solder with inlet and outlet tubes attached to the valve Excessive heat will damage the rubber and plastic components of the valve Pipe supports must be placed a minimum of 16 away from valve DO NOT overtighten unions Adjustable Wrench Phillips Head Screwdriver This valve is NOT factory preset Upon installation the temperature of this valve must be checked and adjuste...

Page 4: ...and reopen the valves after inspection and repair is complete Problem Cause Solution External leaks Damaged cartridge or O rings Replace cartridge with part number 269 2000S Improper water temperature or temperature fluctuation Hot water supply is not 10 above desired set point Increase hot water supply temperature Valve temperature is not properly set Adjust the temperature as shown on page 2 ste...

Page 5: ...1 1 1 1 1 5 198 015 Check Valve 2 2 2 2 2 6 132 055 Retaining Ring 2 2 2 2 2 7 125 001CP Rubber Washer 3 3 3 3 3 8 146 081 U Clip 1 1 1 1 1 9 110 245 Tailpiece Nut 3 3 3 3 3 10 S45 2456 Mounting Bracket Kit optional 1 1 1 1 1 11 129 067 Sweat Tailpiece 3 12 129 068 NPT Sweat Tailpiece 3 13 129 066 NPT Tailpiece 3 14 129 070 PEX Tailpiece 3 15 129 069 PEX Tailpiece 3 Included with Prepack S65 380 1...