Bradley
• 215-1833-4 Rev. A: ECN 17-00-021A
Bowl and Pedestal Assembly (Stainless Steel & Terrazzo)
WF2605, WF2608, WF2705, WF2708
P.O. Box 309
•
Menomonee Falls, WI 53052-0309
•
1 800 BRADLEY
•
262 251 6000
•
bradleycorp.com
(mm)
Rough-In Specifications
Type A
Off-line vent with
supplies from below
7-5/8"
(194)
4"
(102)
2-1/2"
(64)
1" NPT Supplies Through Floor:
Stub Up 2-1/2" (64) Above Floor
Cold
Hot
2" NPT Drain,
Stub Up 3" (76)
Above Floor
54" (1372) Bowl
7-5/8"
(194)
Type B
Centrally rising vent with
supplies from above
1" NPT Supplies From Above
Must Reduce to 1/2" Nom. Copper
Tube on These Centers To Pass
Thru Washfountain
7/8"
(22)
7/8"
(22)
Hot
1-1/2" NPT
Vent to Ceiling
1-1/4"
(32)
4"
(102)
2" NPT Drain,
Stub Up 3" (76)
Above Floor
54" (1372) Bowl
Cold
UPC and IPC restricts the
vertical distance from the fixture
outlet to the trap weir to not
more than 24". Check state and
local codes for variances.
36" (914) Bowl
36" (914) Bowl
Rough-In Notes
1. All pipes and fittings not furnished by Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should be 1", for three washfountains 1-1/2"; for more than three washfountains,
pipe sizes should be increased proportionately.
3. Overhead supplies must be reduced to 1/2" copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
Some optional equipment shown.