Page 42
LAARS Heating Systems
Modbus
Address
R/W
Notes
Map Descriptor Name
BACnet
Data
BACnet
Object Read/Write
74
Read
Lag 5 State
AI
74
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
75
Read
Lag 5 Firing Rate
AI
75
Read
Ccrrent firing rate (0-100%)
76
Read
Lag 6 State
AI
76
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
77
Read
Lag 6 Firing Rate
AI
77
Read
Ccrrent firing rate (0-100%)
78
Read
Lag 7 State
AI
78
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
79
Read
Lag 7 Firing Rate
AI
79
Read
Current firing rate (0-100%)
80
Read
Lead 0 State
AI
80
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
81
Read
Lead 0 Firing Rate
AI
81
Read
Current firing rate (0-100%)
82
Read
Lead Firing Rate
AI
82
Read
Current firing rate of the Cascade Lead (0-
100%)
83
Read
Active CH Setpoint
AI
83
Read
0=None
5 = Start
24 = Error Block
160 = Standby
165 = Check Safety Swtich
166 = Run
177 = Prepurge Open
181 = Parameter Block
183 = Lockout
188 = Testmode
194 = Prepurge Closed
195 = Wait for HIS Free
196 = HIS Preheat/Prespark
200 = Verify Primary SF
217 = interpurge
241 = Postpurge
245 = Trial for Ignition
250 = Trial for Ignition Main
52=Post Purge
0 = no CH source
1 = CH1
2 = CH2
5 = External Demand
89
Read
Boiler Pump Status
AI
89
Read
90
Read
Cascade Master Heat Demand
AI
90
Read
91
Read
Burner 1 Run Time
AI
91
Read
i
128
Read/Write CH1 Enable/Disable
AV
0
Read/Write 0 = Disable; 1 = Enable;
129
Read/Write CH1 Set Point
AV
1
Read/Write
130
Read/Write CH1 P
AV
2
Read/Write
131
Read/Write CH1 I
AV
3
Read/Write
132
Read/Write CH1 D
AV
4
Read/Write
133
Read/Write CH2 Enable/Disable
AV
5
Read/Write 0 = Disable; 1 = Enable;
Read
86
Read
84
CH Set Point Source
Burner Status 1
AI
84
Read
AI
86
Read
Modbus/BACnet Memory Map (continued)