Page 40
LAARS Heating Systems
0
Read
Inlet sensor
AI
0
Read
1
Read
Outlet sensor
AI
1
Read
2
Read
Flue Sensor
AI
2
Read
3
Read
DHW sensor
AI
3
Read
4
Read
System Inlet Sensor
AI
4
Read
5
Read
System Outlet Sensor
AI
5
Read
6
Read
Outdoor Sensor
AI
6
Read
7
Read
Flue Sensor
AI
7
Read
12
Read
Flame Signal 1
AI
12
Read
14
Read
0-10VDC (4-20mA) Input for BMS
AI
14
Read
bit0 = Flow Switch
bit1 = LWCO
bit2 = MRHL
bit3 = SV2 Valve Interlock
bit4 = High Gas Pressure
bit5 = Low Gas Pressure
bit6 = ARHL
bit7 = Condensate Level
bit0 = Field Input 1
bit1 = Field Input 2
0=None
1=Anti-Short Cycle
2=Service
3=DHW
4=Cascade
5=External
6=CH1
7=CH2
10=Anti-Frost
11=Warm Weather Shutdown
bit0 = Run Contact
bit1 = Alarm Contact
bit2 = DHW Pump
bit3 = System Pump
bit5 = Aux Dry Contact 1
bit6 = Aux Dry Contact 2
bit7 = Boiler Pump
bit8 = Aux Powered Contact
bit 0 = N/A
bit 1 = Burner 1 Gas valve 1
23
Read
0-10VDC (4-20mA) Output for Pump Spee
AI
23
Read
mV
27
Read
Modulating Fan 1 - Speed
AI
27
Read
RPM
33
Read
Modulating Burner1 Firing rate
AI
33
Read
%
LOW FLOW ERROR = 0
LOW WATER CUT OFF ERROR = 1
MANUAL RESET HIGH LIMIT ERROR = 2
BLOCKED FLUE ERROR = 3
HIGH GAS PRESSURE ERROR = 4
LOW GAS PRESSURE ERROR = 5
AUTO RESET HIGH LIMIT ERROR = 6
SPARE SAFETY CHAIN ERROR = 7
OUTLET PROBE ERROR = 8
OUTLET PROBE DRIFT ERROR = 9
OUTLET PROBE HIGH LIMIT ERROR = 10
FLUE PROBE ERROR = 11
FLUE PROBE DRIFT ERROR = 13
FLUE PROBE HIGH LIMIT ERROR = 14
INLET PROBE ERROR = 15
DELTA T ERROR = 16
Read
35
Read
21
Read
22
19
Read
20
Read
Modbus
Address
R/W
18
Read
Safety Chain Status
Non-safety Chain Status
Demand source
Gas and Pilot Valve Status
AI
22
AI
20
Lockout Code
AI
35
Read
Read
Digital Output Status
AI
21
Read
Read
AI
19
Read
AI
18
Read
Notes
Map Descriptor Name
BACnet
Data
BACnet
Object Read/Write
7.F Modbus/BACnet Memory Map