B O S T E C   L I M I T E D .  

 

Start up Procedure cont…

 

 

Note 

We only recommend the use of 

Andrea Filters 

 other inferior filters do 

not offer the same performance. Contact us for further details on this.  

Switch on the Mains Isolator. 

Press the START button 

 in a few moments the LED Lights (if fitted) will 

turn on and the extraction system will be ready. 

Check  the  Manometer  (if  fitted)  as  this  tells  you  if  the  filters  require 
changing. 

 

 

 

 

 

If the 

RED 

Liquid moves into the 

RED 

Zone you must change the filters 

immediately (see previous page on how to change filters). 

If the 

RED 

Liquid is in the 

Green 

or 

Amber 

Zones you are ready to spray. 

 

Shutdown Procedure  

Press the STOP button 

 the booth will turn off the fans and the lights. 

Note 

We recommend leaving the Spray Booth switched on and extracting air 

after the spraying has finished as many of the VOC Gases will still be 
airborne for a significant period after the spraying has ceased.  

Summary of Contents for 2F33B 1D 1L

Page 1: ...BOSTEC LIMITED Dry Filter Spray Booth Manual Dry Filter Spray Booth Manual Volume 1 ...

Page 2: ... N G T E C H N O L O G I E S Operating Servicing Fault Finding Sample Copy Ltd Model No 2F33B 1D 1L 3rd January 2020 BOSTEC Limited Jct 21 Trading Estate Gorse Street Chadderton Oldham OL9 9QH T 0161 620 4091 E info bostec co uk ...

Page 3: ...1 WARNING 1 SAFETY INFORMATION 2 You should 2 Appropriate PPE we would recommend 2 Spray Booth Operation 3 Maintenance Procedures 6 Daily 6 Weekly 6 Monthly 6 Annually 14 months maximum 6 Fanset Information 7 Drawings 13 Commissioning Form 14 ...

Page 4: ...ed to create a simple to follow manual Please use the icons for a quick guide to the most important information If you have any questions please contact us at info bostec co uk WARNING If incorrectly used or maintained Spray Booths can be hazardous It is vital that this manual is followed the spray booth is only operated by trained personnel and only serviced by Qualified Engineers Commissioning R...

Page 5: ...rsons The law requires you to service any Spray Booth LEV every 14 months Contact us to find out how we can help with this Never consume food or drink in the Spray Booth area Ensure the area around the Spray Booth is kept clean and tidy Always check the operation of any safety equipment prior to use of the Spray Booth Appropriate PPE we would recommend Safety Glasses or Goggles Protective safety s...

Page 6: ...B O S T E C L I M I T E D 3 Spray Booth Operation Check all safety devices are in good condition and operating correctly Check filters are installed correctly as follows Start up Procedure ...

Page 7: ...meter if fitted as this tells you if the filters require changing If the RED Liquid moves into the RED Zone you must change the filters immediately see previous page on how to change filters If the RED Liquid is in the Green or Amber Zones you are ready to spray Shutdown Procedure Press the STOP button the booth will turn off the fans and the lights Note We recommend leaving the Spray Booth switch...

Page 8: ...ights will switch off the fan s will continue to run for a preset time to ensure the minimum clearance time as set out in the commissioning report has been met When you want to start spraying again simply press the START button again this will override the timer system and turn the lights back on When the booth is not in use isolate the power at the main electrical isolator ...

Page 9: ...ck and re adjust as required as the belts may stretch as they become warm From inside the extraction chamber where possible inspect and clean the fan impellor if any paint buildupisapparent Followingcleaninglightly greaseeach impellor to aid easy cleaning next time Check and clean the internal finger guard if any paint buildup is apparent Annually 14 months maximum A full Thorough Inspection and T...

Page 10: ...B O S T E C L I M I T E D 7 Fanset Information ...

Page 11: ...B O S T E C L I M I T E D 8 ...

Page 12: ...B O S T E C L I M I T E D 9 ...

Page 13: ...B O S T E C L I M I T E D 10 ...

Page 14: ...B O S T E C L I M I T E D 11 ...

Page 15: ... is operating correctly The lights are on but there appears to be no extraction 1 Check the starter for the fans is working 2 Check the belts on the fans are not slipping or broken 3 Check the fanset is free to rotate There is only partial or reduced extraction 1 Check the condition of the filters 2 Check the fan is rotating in the correct direction 3 Check all fans are working at the same time on...

Page 16: ...B O S T E C L I M I T E D 13 Drawings ...

Page 17: ...B O S T E C L I M I T E D 14 Commissioning Form p ...

Page 18: ...B O S T E C L I M I T E D 15 ...

Page 19: ...B O S T E C L I M I T E D 16 ...

Reviews: