1..8
10
24 Vdc
CS-AMS-8
+
-
24 Vdc
9
10
Open collector
Max. 50mA
CS-AMS-8
+
-
ControlSpace
®
AMS-8 includes one GPIO / Ethernet card (see also chapter 3.2).
Up to 40 GPIO contacts (8 per rack, max 5 rack frames in total) can be used to trigger up to 40 messages,
up to 40 room combine presets or the Room Standby function (‘mute’) on different or all outputs.
The contacts are triggered by applying 24VDC between the specific contact and the common ground pin.
NOTE:
A ‘Pulse’ contact will play a message once. A ‘Hold’ contact will play and repeat a message until the
contact is released. Use a hold contact to activate room combining or standby mode (release this contact to
de-activate these two functions)
Characteristics
• 8 isolated inputs
• 1 isolated output
• Inputs can be used for message routing, room combining or to put an output or group of outputs in standby
mode (outputs will return to default value when contact is released again)
• Open collector output is activated when one of the eight inputs is activated
Wiring diagram of the 8 input contacts
Wiring diagram of open collector output
3. System Installation
3.9 General Purpose Inputs / Outputs (GPIO)
CS-AMS-8
CS-AMS-8
Summary of Contents for ControlSpace AMS-8
Page 27: ...English 27 ...
Page 29: ...English 29 ...
Page 55: ...55 55 Dansk ...
Page 57: ......
Page 83: ...83 Deutsch 83 ...
Page 85: ......
Page 111: ...111 Español 111 ...
Page 113: ......
Page 139: ...139 Français 139 ...
Page 141: ......
Page 167: ...167 167 Italiano ...
Page 169: ......
Page 195: ...195 Nederlands 195 ...
Page 197: ...197 Nederlands 197 ...
Page 223: ...223 223 Polski ...
Page 225: ...English ...
Page 251: ...251 Svenska ...
Page 253: ...253 Svenska ...
Page 254: ......
Page 255: ......
Page 256: ......