RE 30162-B/04.11 | SYHNC100-SEK...X
Bosch Rexroth AG
23/
44
Assembly
Recommended accessories
6.2
The following accessories are recommended for the connection of the
SYHNC100-SEK...3X controller assembly. These accessories are not included in
the scope of delivery, and can be ordered separately from Bosch Rexroth.
Accessories
Table 6:
Component
Material number
RS232 interface cable, 1:1, length: 3 m
R900776897
USB RS232 converter
R901066684
Cable set VT17220-1X/HNC100...3X, length 2 m,for analog
signals (connection X2A) and digital position measurement
systems (connection X8M) with HD plug-in connector and open
breakout cable for SYHNC100-SEK...3X
R901189300
Plug-in connector type 6ES7972-0BA41-0XA0 for PROFIBUS DP
R90050152
SYHNC100-SEK...3X assembly
6.3
Lay the cables and lines so that they cannot be damaged and no one can trip
f
over them.
By snapping the housing of the SYHNC100-SEK...3X on a conductive
f
assembly rail, the earth connection to the control cabinet rear wall is
established. This constitutes the HF earthing of the SYHNC100-SEK...3X.
No silicone-containing sealing, adhesive, or insulating agents must be used.
f
Ensure a maintenance-friendly installation, i.e. simple access to the
f
connection lines. Free access to the connection side must be guaranteed.
Before installation note down the information on the nameplates. If, after the
f
installation, nameplates are no longer visible or legible, these data will be
quickly available to you at any time.
Place of installation
6.3.1
Do not install the HNC next to power electronics (e.g. frequency converters, etc.)
The power pack of the SYHNC100-SEK...3X should be installed as close to the
SYHNC100-SEK...3X as possible.
Voltage supply
6.3.2
The connection should be as short as possible. Pass supply and return lines
f
(+24 V/GND) together. Voltage 18 - 30 V.
Load lines of two individual wires (voltage supply) are to be passed in a
f
parallel or drilled form.
Supply of external components
6.3.3
When supplying a 24 V encoder, the input voltage of the SYHNC100-SEK...3X
at X1S must comply with the encoder's requirements (e.g. 24 V +/-5 %, residual
ripple <500 mV).
Analog components like pressure cells can be supplied via the sockets X2A1...4.
Prerequisite: The supply of the SYHNC100-SEK...3X corresponds to the
requirements of the pressure tapping point. Further notes with regard to currents,
etc. are available in the data sheet RE 30162.