4.3
Overcurrent protection
Protect the components against overcurrent:
●
Branch circuit protection has to be provided externally.
For the North American and Canadian sales region, individual branch
circuit protection on the mains side is mandatory before each device.
●
Size the branch circuit protection according to the "Branch circuit protec‐
tion fuse" data (see Ratings and dimensions)
●
Install fuses for the control voltage supply
4.4
Short circuit protection
Integral solid state short circuit protection does not provide branch circuit pro‐
tection.
UL: Branch circuit protection must be provided in accordance with the Manu‐
facturer Instructions, National Electrical Code and any additional local codes.
CSA (for Canada): Branch circuit protection must be provided in accordance
with the "Canadian Electrical Code, Part I".
18/29
Instructions for use
IndraDrive Mi KMV03 Distributed Supply Unit KNK03 Distrib‐
uted Mains Filter
Bosch Rexroth AG R911374765_Edition 01