8.8
Analog Voltage Input
AD
Analog/digital converter
Fig. 8-32:
Analog Voltage Input
Data
Unit
Min.
Typ.
Max.
Allowed input voltage
V
-30
+30
Working range input voltage U
on_work
V
-10
+10
Input resistance R
u
kΩ
150
300
Input bandwidth (-3 dB)
kHz
1,3
Common-mode range
V
-30
+30
Common-mode rejection
dB
50
Relative measuring error at 90%
U
on_work
%
-1
+1
Resolution
Bit
14
1)
13
2)
Cables
For cable lengths > 30 m, only use
shielded cables.
1)
Applies to: Cxx02 control sections (X32), optional I/O extension
DA (X38), HCS01 drive controllers (X32)
2)
Applies to: Control sections with extended scope CSx02.1B
(X35), CDB02.1B (X36)
Tab. 8-35: