IndraControl XFE 01.1
Mounting
Bosch Rexroth AG
R911345570, Edition 06
●
They have a counterpressure against the engaging forces when mounting the modules in
series to the control.
•
Do not route cables parallel to motor cables or other strong interference sources to avoid the
coupling of interferences
•
The LED displays may not be hidden
•
Observe the bending radius of the cables used when laying the connecting lines
•
Use strain reliefs for all cables
•
Keep the maximum distance possible from interference sources
•
Provide minimum distances for sufficient cooling. Refer to the operating instructions of the XM
control, see
30 mm
30 mm
100 mm
100 mm
30 mm
Fig. 7: Minimum distances for the circulation of ambient air
In case of a several line design, the supply air has to be measured under each line and its limit value has
to be observed. For information on ambient temperatures, refer to
•
Additionally, provide sufficient distance for mounting, dismounting, plugs and cables.
•
Use only cables approved for temperatures of at least +60°C. In case of ambient temperatures
above +55
C, use cables approved for temperatures of at least +75°C.
10.3 Mounting
NOTICE
Damages at the contacts by tilting the modules
Attach the modules vertically on the mounting rail and remove the modules
vertically from the mounting rail.