Switch position
UPS time
0
5 seconds
1
60 seconds
2
120 seconds
3
180 seconds
Fig.6-4:
Switch position 0 to 3
Switch position 4 to 7 (for commis‐
sioning)
If switch positions 4 to 7 are used, the timer (time delay of 120 sceonds) inte‐
grated in the UPS is switched off. Thus, unnecessary waiting times, e.g. dur‐
ing commissioning, are avoided. After commissioning reset the switch to the
switch positions 0 to 3.
We recommend switch positions 4 to 7 exclusively for commis‐
sioning to avoid waiting times.
Switch position
UPS time
4
5 seconds
5
60 seconds
6
120 seconds
7
180 seconds
Fig.6-5:
Switch position 4 to 7
Switch position 0
If the rotary switch is set to 0, UPS operation is 5 seconds with a time delay
of 120 seconds.
Switch position 1
If the rotary switch is set to 1, UPS operation is 60 seconds with a time delay
of 120 seconds.
Switch position 2
If the rotary switch is set to 2, UPS operation is 120 seconds with a time de‐
lay of 120 seconds.
Switch position 3
If the rotary switch is set to 3, UPS operation is 180 seconds with a time de‐
lay of 120 seconds.
Switch position 4
If the rotary switch is set to 4, UPS operation is 5 seconds without time delay.
Switch position 5
If the rotary switch is set to 5, UPS operation is 60 seconds without time de‐
lay.
Switch position 6
If the rotary switch is set to 6, UPS operation is 120 seconds without time de‐
lay.
Switch position 7
If the rotary switch is set to 7, UPS operation is 180 seconds without time de‐
lay.
6.4.4
Timing Depending on the Position of Rotary Switch S1 and Settings in
the UPS-NT Control Software
For further information on the UPS-NT Control software, please refer to the
relevant documentation of the connected device, see also
.
Overview
Example: Switch position 2, Shutdown Delay Time = 45 seconds
DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
Bosch Rexroth AG
33/63