Installation 59/104
RE 92076-01-B/10.2017, A4... with HS5E pilot control valve/Series 3x,
Bosch Rexroth AG
CAUTIOn
Uncontrolled rise in pressure!
Risk of injury.
▶
You must carry out wiring such that the pressure transducer is not short-
circuited, since in the absence of a pressure signal, the control electronics can
no longer detect the pressure, which results in an uncontrolled rise in pressure.
We have found that locations that are not in the immediate vicinity of the pump and
which are located downstream of the (flexible) pressure hose are favorable for
attaching the pressure transducer:
•
Always between the pump and a check valve that may be installed
•
Do not use Minimess hoses
We recommend suspended installation of the pressure transducer to rule out air
bleeding problems (and any associated control oscillations) right from the start.
If the installation position of the pump leads to a pressure transducer that is
installed directly into the pump being positioned vertically, we recommend
choosing a different installation position for the pressure transducer.
The HM20 pressure transducer has a two-wire current interface and it can be
connected to the pilot valve via the central connector.
The supply voltage for the pressure transducer must comply with the specification.
For more detailed information about the pressure transducer, see data sheet 30272.
The HM20 pressure transducer has a 0...+10 V voltage output as the actual pressure
value signal and you can connect it to the pilot valve.
The supply voltage for the pressure transducer must comply with the specification.
For more detailed information about the pressure transducer, see data sheet 30272.
Place of installation of the
pressure transducer
Mounting orientation
of the pressure transducer
Pressure transducer HM20
(current)
Pressure transducer HM20
(voltage)