126
en | Multifunction power supply, large | PRA-MPS3
PRAESENSA
2019.11 | V1.00 |
Installation manual
Bosch Security Systems B.V.
11.7
Technical data
Electrical
Power transfer
Mains power supply input
Input voltage range
Input voltage tolerance
Frequency range
Inrush current
Power factor (PF)
Leakage current to safety ground
115 to 240
VRMS
102 to 264
VRMS
50 to 60
Hz
<
20
A
0.9 to 1.0
<
0.75 mA (120
V),
<
1.5 mA (240
V)
Battery power supply input
Nominal DC input voltage
DC input voltage tolerance
Maximum current
Under-voltage protection
12.6
V
9 to 15
V
90
A
<
9
V
Battery charger
Nominal charging current
Nominal float voltage
Float voltage control
Temperature sensor NTC
Charging temperature range
8.5
A
13.5
V
-21.9
mV/°C
10
kohm / β = 3984
K
-15 to 50
°C
48
VDC outputs (1‑3)
Nominal DC output voltage
Maximum continuous current
Maximum peak current
48
V
5.5
A
7.0
A
24
VDC output
Nominal DC output voltage
Maximum continuous current
Maximum peak current
24
V
0.7
A
0.9
A
Lifeline DC outputs (1‑3)
Nominal DC output voltage
Maximum continuous current
Maximum peak current
18
V
0.7
A
1.0
A
Power over Ethernet (PoE 1‑2)
Nominal DC output voltage
Standard
Maximum PD load
48
V
IEE
802.3af (mode B)
12.95
W
Power consumption
Mains powered
Active mode, all outputs loaded
Battery powered
Unloaded
<1000
W
5.2
W
Summary of Contents for PRAESENSA
Page 1: ...PRAESENSA Public Address and Voice Alarm System en Installation manual ...
Page 2: ......
Page 193: ......