6 720 808 907 (2014/04)
MM100
Commissioning | 89
4
Commissioning
4.1
Setting the code switch
When the code switch is in a valid position, the indicator lights
up green continuously. When the code switch is in an invalid
position or an intermediate position, the indicator does not
light up initially. It then starts to flash red.
Assigning heating circuits via the code switch:
•
1 heating circuit:
Code switch on
1
•
2 heating circuits:
Heating circuit 1 = code switch on
1
;
heating circuit 2 = code switch on
2
•
3 heating circuits:
Heating circuit 1 = code switch on
1
;
heating circuit 2 = code switch on
2
;
heating circuit 3 = code switch on
3
etc.
Assigning cylinder primary circuit (1 or 2) via code switch:
•
1 cylinder primary circuit: code switch on
9
•
2 cylinder primary circuits:
Cylinder primary circuit 1 = code switch on
9
;
Cylinder primary circuit 2 = code switch on
10
4.2
System and module commissioning
4.2.1 Settings for heating circuit
1. Assign the module to a heating circuit (1...4).
2. Set the code switch on other modules as applicable.
3. Connect the entire system to the mains voltage.
When the module indicator lights up green continuously:
4. Commission and set up the user interface as described in
the accompanying installation instructions.
4.2.2 Settings for cylinder primary circuit
1. Assign the module to a cylinder primary circuit (9...10).
2. Set the code switch on other modules as applicable.
3. Connect the entire system to the mains voltage.
When the module indicator lights up green continuously:
4. Commission and set up the user interface as described in
the accompanying installation instructions.
5
Troubleshooting
The indicator shows the operating condition of the module.
First make all electrical connections and then
carry out the commissioning!
▶ Follow all installation instructions for all
components and assemblies in the
system.
▶ Make sure that multiple modules do not
have the same coding.
▶ Only switch on the power supply when all
modules are set up.
NOTICE:
Connected pumps can start as soon
as the system is switched on unless the control
unit has detected the module.
▶
Fill the system before switching it on
so
that the pumps do not run dry.
When a heating circuit is connected directly to
the heat appliance, the code switch must not
be set to 1 on any of the modules. In this case,
the first heating circuit after the low loss
header is heating circuit 2.
When a cylinder primary circuit is connected
directly to the heat appliance, the code switch
must not be set to 9 on any of the modules. In
this case, the cylinder primary circuit after the
low loss header is cylinder primary circuit 2.
Only use genuine parts. Any damage resulting
from spare parts that are not supplied by the
manufacturer is excluded from liability.
If a fault cannot be rectified, please contact the
responsible service engineer.
0
1
2
3
4 5 6
7
8
9
10
6 720 645 409-20.1o
Summary of Contents for MM100
Page 105: ...6 720 808 907 2014 04 MM100 105 Fig 15 1 2 3 4 5 6 7 8 9 10 0 6 720 645 409 25 1O ...
Page 113: ...6 720 808 907 2014 04 MM100 113 ...
Page 114: ...6 720 808 907 2014 04 MM100 114 ...
Page 115: ...6 720 808 907 2014 04 MM100 115 ...
Page 116: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www bosch thermotechnology com ...