6 720 808 907 (2014/04)
MM100
86 | Product details
2.4
Cleaning and care
▶ If required, wipe the enclosure with a damp cloth. Never
use chemically aggressive or acidic cleaning agents.
2.5
Supplementary accessories
For precise information regarding suitable accessories, refer to
the catalogue.
•
For heating circuits with or without mixing valve actuators
and constant heating circuits:
– Heating pump; connection to PC1
– Flow temperature sensor for low loss header (optional;
not possible with all user interfaces); connection to T0
– Temperature switch; connection to MC1; when limit
temperature is exceeded, power supply to terminal 63
- PC1 is interrupted; if there is no temperature switch in
the heating circuit without mixer or in the constant
heating circuit, connect jumper (
page 100) to MC1 included in standard delivery.
•
Additional accessories for heating circuit with mixer:
– Mixing valve actuator; connection to VC1
– Flow temperature sensor in assigned heating circuit;
connection to TC1
•
Additionally, for a heating circuit in conjunction with a heat
pump (heating/cooling):
– Dew point monitor; connection to MD1; sends a signal
to the control when the dew point is reached, in order
to avoid condensate formation by further cooling, and
stops the heating pump
•
Additionally, for a constant heating circuit:
– External signal for heat requirement; connection to
MD1 (the pump is only switched on if the external heat
requirement is enabled on the user interface)
– Mixing valve actuator (optional); connection to VC1
– Flow temperature sensor in assigned heating circuit
(optional); connection to TC1
•
For cylinder primary circuit (e.g. after low loss header):
– Cylinder primary pump; connection to PC1; connect
jumper (
– DHW circulation pump (optional); connection to VC1
(terminal 43: DHW circulation pump phase/terminal
44: not assigned)
– Flow temperature sensor for low loss header (optional;
not possible with all user interfaces); connection to T0
– Cylinder temperature sensor; connection to TC1.
Installation of additional accessories
▶ Install additional accessories according to legal
requirements and the instructions supplied.
Unless otherwise stipulated in the instructions supplied with
the dew point monitor or heat pump:
▶ Install condensation point sensor as near as possible on the
buffer cylinder or on the coolest point of the system.
▶ Connect max. 4 dew point monitors in parallel to MD1.
Temperature sensor
capturing range
•
lower fault limit
•
display range
•
upper fault limit
•
<-10 °C
•
0 ... 100 °C
•
> 125 °C
Permissible ambient
temperature
0 ... 60 °C
IP rating
•
For installation in
heat source
•
For wall-mounted
installation
•
Determined by the IP rating of
the heat source
•
IP 44
Protection class
I
ID no.
Data plate (
°C
°C
°C
8
25065
38
7174
68
2488
14
19170
44
5730
74
2053
20
14772
50
4608
80
1704
26
11500
56
3723
86
1421
32
9043
62
3032
–
–
Table 4 Test values for the flow temperature sensor
(included in standard delivery)
Technical data
Table 3
Summary of Contents for MM100
Page 105: ...6 720 808 907 2014 04 MM100 105 Fig 15 1 2 3 4 5 6 7 8 9 10 0 6 720 645 409 25 1O ...
Page 113: ...6 720 808 907 2014 04 MM100 113 ...
Page 114: ...6 720 808 907 2014 04 MM100 114 ...
Page 115: ...6 720 808 907 2014 04 MM100 115 ...
Page 116: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www bosch thermotechnology com ...