13.10 Outdoor Board Fuse
Figure 47
The System will not work if this fuse is
blown.
Fuse Type 250V/30A
Function Protect control board
Power off unit
No
Did the ODU motor
fail? 1
Replace ODU motor
Yes
Replace control board,
refer to instructions
included with spare board
No
Did the compressor
fail? 2
Replace compressor
Yes
Power off unit
Did the fuse blow
on the outdoor board?
No service required
No
Yes
Fuse
Location
IDS 2.0 3T ODU board
IDS 2.0 5T ODU board
Fuse
Location
Outdoor Board Fuse
1) See Section 13.6
2) See Section 13.8