12.2 Fault Code and Limited Condition Descriptions
Limited Condition Status codes
are displayed when a condition exists that
could harm the unit. To protect itself, the unit continues to run, but with limited
compressor frequency. When these protection codes are visible, the unit is still
functioning, just not according to its normal logic. If condition worsens/persists, a
fault code will be displayed and the compressor will shut off . For Limited Condition
Status codes, no service is required. Service may be recommended for active fault
codes, see fault code troubleshooting section for more detail.
Limited Condition
Status code
Fault Code
Fault Code Description
Potential Cause
C3
T3 sensor is not reading correctly in cooling.
Wrong location of T3 sensor
Failed T3 sensor
Failed T4 sensor
E4
Temperature sensor fault
Temperature sensors failed
Wrong wire connections of sensor
Ambient temperature beyond system operation range
U**
E5
High/low voltage protection.
Power supply ≥270V
Power supply <172V
Control board issue
E6
Outdoor DC fan motor fault.
Motor failed
Fan blade damaged or blocked
Extreme weather conditions
Electrical issue
E7
T5 sensor not reading correctly.
Wrong location of T5 sensor
Wrong connection on control board of T5&Tf
T5 sensor failed
E9
EEPROM IC20 fault.
EEPROM IC20 poor contact
EEPROM IC20 improperly installed
H0
Communication fault in EEPROM IC14 chip.
Control board failed
H8
Pressure transducer (PT) fault.
Pressure transducer wiring not secure
Pressure transducer failed
F**
P0
Control board is over-heated.
Poor heat dissipation
Tf sensor failed
Wrong connection on control board of T5&Tf
Outdoor motor failed, causing control board to
overheat
P1/F1
High pressure protection.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Over charged
Table 27
Fault code and limited condition status table
** If the fi rst digit shown on the control board LED is one of the following protection codes (followed by two
numerical digits which show the current compressor frequency in Hz), the unit will continue to run but in a
limited condition. The only exception is when the system is in defrost mode, which only displays "dF" (without
any numerical digits following).
Fault codes
are displayed when an abnormal condition exists that could harm the
unit. Fault codes cause the compressor to shut off and force the unit into standby
mode until the abnormal condition goes away. When the abnormal condition
ceases, the unit will restart and operate as normal. The only exception is H5 which
requires a hard restart. Service may be recommended for active fault codes, see
fault code troubleshooting section for more detail.