12.3.10 P1/F1 Troubleshooting
LED display output:
P1/F1
Description:
High pressure protection
Possible causes:
Poor heat exchange on coil (cooling mode – outdoor coil, heating mode – indoor coil)
Fan motor failure (cooling mode – outdoor fan, heating mode – indoor fan)
Service valves not open
TXV/EEV/filter drier blocked
Over charged
Table 38
Procedure:
Figure 25
Are you running in
force mode?
Yes
Is there still a fault
code?
Is ambient
temperature >
120F?
No
Yes
Quit force mode
No
Yes
Is the system
overcharged
Yes
Follow IOM to adjust
refrigerant
No
Did the high pressure
switch fail?2
Yes
Replace HPS
No
Restart system
Check for abnormal
pressure1
No
No service required
1) See Section 13.1
2) See Section 13.5