C5
Bypass valve damaged or disconnected (only outdoor GWH 16 /20 /26)
Characterístic:
Solenoid valve (proportional valve normally closed and controlled with 0 – 24 V dc)
C7
No rotational speed sensor signal from primary fan
Characteristic: Primary Fan (DC centrifugal fan)
Lock Out Error
appliance enters in lock out immediately
Check bad wire connection in the
connector in the back cover of
control unit
Problem solved?
Fan unplugged / cables
disconnected or not correctly
attached
Yes
No
Measure output signal from
control unit
End
Solenoid valve is
connected?
Ensure that cables are
connected
Problem solved?
Note: error only displayed if valve was
requested to activate due to temperature
variations above set point
Damaged Valve
yes
end
No
Replace Valve
Run the calibration “bP”
function in parameter PA
Problem solved?
yes
No