Operating Instructions
31
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
The fan remains running until the Purge menu is exited, to do
so:
▶ Press the button
.
6.5.3 SA (Settings)
Fig. 33
SA - Settings
This menu provide access to several parameters.
▶ Access to information / adjustments menu.
Display shows
P4 (Information)
.
▶ Press the button
until the display shows
SA
(Settings)
.
▶ Press the button
.
Display shows
E
.
▶ Press buttons
or
to choose the following
information.
–
E Exit
–
A1 Recirculation
–
A8 Startup Delay
–
A9 Units Set
–
Ab Region Selection
–
rS Recirculation Settings
▶ Press the button
to select the desired information.
A1 Recirculation
Choosing a recirculation program:
▶ Press the button
.
▶ Press buttons
or
to scroll through the options.
–
OF OFF
–
HR House Recirculation
-
Hot water readily available at faucets.
–
tI Tank Loading Internal NTC
- Tank loading using the water heater’s inlet water
temperature sensor to control the pump.
–
tE Tank Loading External NTC
- Tank loading using the external temperature sensor to
control the pump
–
tA Tank Loading Aquastat
- Tank loading using the external temperature sensor to
control the pump.
▶ Press the button
to exit recirculation menu.
A8 (Startup Delay)
Fig. 34
A8- Startup Delay
This menu allows programing a burner start delay between 0
and 60 seconds, after detecting water flow.
▶ Access to information / adjustments menu.
Display shows
SA (Settings)
.
▶ Use the buttons
or
to choose
A8 (Startup Delay)
.
▶ Press the button
.
Display shows
Startup Value(s)
.
▶ Press the buttons
or
to define, in seconds, the
delay to start-up after detection of the water flow.
▶ Press the button
for 3 seconds to save the desired
value.
▶ Press the button
to exit
A8 (Startup Delay)
menu.
A9 (Units Set)
This menu allows you to choose the units visible on the display.