Problem solving
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
46
CA
Water flow above 9.2gpm.
▶ Disconnect the appliance and purge hydraulic circuit
to remove air.
▶ Install water flow restrictor.
▶ Check water pressure does not exceed
150psi.(
section
CE
Flue blockage detected during operation due to
excessive pressure on the siphon.
▶ Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
▶ Check air openings and exhaust opening for
obstructions and reset the error.
▶ Check if the air filter is dirty or clogged.
▶ Perform gas and air tuning (
▶ Contact Bosch support line for additional
information and assistance in case of installation in
dusty areas.
CF
Flue blockage detected during operation due to
insufficient combustion air.
▶ Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
▶ Check air openings and exhaust opening for
obstructions and reset the error.
▶ Check if the air filter is dirty or clogged replace it if
needed.
▶ Perform gas and air tuning (
If the problem persists:
▶ Contact Bosch support line for additional
information and assistance in case of installation in
dusty areas.
E0
Electronic control unit internal error.
▶ Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
▶ Replace electronic control unit.
E1
Hot water temperature above 194 °F (90 °C).
Appliance burner cut off to prevent scalding and
reactivation after cooling down.
▶ Disconnect the appliance and purge hydraulic circuit
to remove air.
If the problem persists:
▶ Reduce setpoint temperature to minimize
temperature instabilities.
E3
Flue gases temperature above 167 °F (75 °C) or 2
minutes above 145 °F (63 °C).
Appliance burner cut off to prevent overheating.
▶ Descale appliance (
▶ Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
▶ Check sensor resistance [15] (
replace the sensor if it is not according to
specification.
Display
Description
Solution