en | Release Notes for Version 1.10
Analog Addressable Fire Panels
F.01U.075.638 | 08 | 2012.08
Release Notes
Bosch Security Systems, Inc.
–
NAC appliances (refer to
FPA-1000-UL NAC Compatibility List
, P/N F.01U.075.636):
–
New Wheelock and System Sensor devices have been added to the compatible
devices’ list
–
Gentex devices registered
–
Mainboard/Option Bus NAC patterns include Gentex
–
Built-in synchronization for appliances from Gentex
–
NAC patterns for global gas alarm zone include Temporal Code 4.
–
Programming option for IP reporting communication with the Advanced Encryption
Standard (AES)
–
Programming option for SIA 300 and Modem IIIa
2
reporting formats: With text or without
text
–
Programming option for silence operation for relays and City Ties
–
Programmable reset enable/disable option of the auxiliary power supply AUX/RST upon
panel reset
–
Programming options for sequential reset of Mainboard and Option Bus relays
–
Global delay alarm option
–
Programming option for sandwich alarm allows time-triggered phased evacuation
(evacuation floor above, floor below)
–
Dual-zone alarm allows for programming a dual-zone dependency
–
Auto logout indication at Level 3
–
Simplified software version indication (refer to
Section 1.2 Version Naming of the
–
Translation of the panel MMI and Web pages into the languages Portuguese and Spanish
–
New features on the Web pages:
–
Off-line configuration tool
–
Online help
–
Allows for comparing and printing the programmed configuration
–
Allows timezone offset for time synchronization with PC
7.2
Issues Fixed in Version 1.10
–
Gas alarm:
Gas alarms are reported to the central station receiver as event type Fire
Supervisory, if Modem IIIa
2
format is programmed. This fixes an issue that Gas alarm is
not sent to the central station receiver.
–
History records for manual/automatic communicator tests:
Each communication test is
recorded in history. It was not recorded in previous versions.
–
Fire trouble/restoral event codes:
If Modem IIIa
2
format is programmed, Fire trouble/
restoral event codes are transmitted, instead of general trouble/restoral event codes.
–
Confirmation for remote programming access
: As soon as the option
Confirm At Panel
is
enabled from the menu, web programming is allowed for 25 minutes. Remote
programming is disabled 25 minutes later.
–
Phone line 1 disconnection:
The panel would sometimes indicate that the phone line 1
was disconnected after being installed for some period of time, preventing the DACT
from transmitting reports via PSTN.
7.3
Known Issues in Version 1.10
–
Level 3 PIN login is blocked on the Web page
: Sometimes Level 3 PIN cannot login any
more. The user must reset the Level 3 PIN from the panel menu.
–
Panel reset:
When resetting the panel, no fire restoral messages will be sent.