Analog Addressable Fire Panels
Release Notes for Version 1.14 | en
9
Bosch Security Systems, Inc.
Release Notes
F.01U.075.638 | 08 | 2012.08
3
Release Notes for Version 1.14
3.1
New Features in Version 1.14
No new features introduced in this version.
3.2
Issues Fixed in Version 1.14
–
SLC Class A open issue:
Panel may take longer than 200 seconds to reinitialize devices
affected by an open on a Class A SLC.
–
Device activate/deactivate:
FAA-326-B6S, FLM-325-SOM series cannot activate/
deactivate after cycling Aux power during an event.
–
Option Bus issues:
Shorting of the option bus does not list troubles for each device that
is missing. Earth grounding of the option bus causes trouble condition to cycle.
–
Auto calibration issue:
If an alarm, trouble, or supervisory condition exists and there is a
power loss on the auxiliary power supply, when the power is restored and the smoke
detectors recalibrate, pre-existing conditions are not reported.
–
Battery charger voltage level issue:
An issue that no trouble is reported when the
battery charge level was below 24 V has been corrected.
–
SLC intermittent open issue:
If the SLC loop is intermittently open and closed, troubles
will be reported for the wrong devices.
3.3
Known Issues in Version 1.14
–
incorrect temporal pattern:
FAA-325-B6S may produce an incorrect temporal pattern for
the first cycle.
–
Reduced system initialization speed:
On large systems with many FMR-1000
annunciators, tupdating annunciator status and initializing the system will take more
time. Please use the battery calculator to plan your system to keep it within the specified
time frame.
–
Incorrect Alarm Verification Time:
The Inguide incorrectly lists the alarm verification
time of 60-120 seconds. This will be corrected to 90-180 seconds range with the next
update of the document.
–
Zone limitation:
A maximum of four FAD-325-R Duct relays can be activated by a single
zone to meet the 10 second time limitation. If more than four FAD-325-R Duct relays are
needed, assign to separate zones.
–
Presignal delay issue:
Presignal does not delay the City Tie reporting until the expiration
of the timer.
–
PAS delay issue:
PAS does not delay the off premise reporting. Activation of the event
starts an immediate report.
4
Release Notes for Version 1.13
4.1
New Features in Version 1.13
No new features introduced in this version.