6 720 803 029 (2011/08)
Modules for control units CSM 7x0, CFB 8x0 and CFB 9x0
26
|
Module mounting for control unit CFB 840
z
Position terminal cover and secure with the screws.
z
Test the module function.
More detailed information can be found in the operating and servicing
instructions for control unit CFB 840.
USER INFORMATION
The connector clips are locked to prevent slippage.
z
When removing the terminals press the locking tab upwards.
USER INFORMATION
If there is no 230 V power supply for the module or one of its 230 V
components (e.g. plug-in connection has not been made), the relevant
components (e.g. pumps) will not be activated.
You
cannot
recognise this error on the module in question since the
LED and the control functions work independently of this power
supply. Check cable connections thoroughly before re-fitting controller
casings.