30
en | Technical Specifications
FCS-320-TM Aspirating Smoke Detector
F.01U.130.928 | 1.0 | 2009.11
Operation Guide
Bosch Sicherheitssysteme GmbH
Three way tap (FAS-ASD-3WT)
Ceiling lead-through (FAS-ASD-CLT) with aspiration hose (FAS-ASD-AHC)
Features
With 3 transition threads for connection to a
25 mm pipe system
Operating pressure
Max. 10 bar
Housing material
PVC plastic
seal
Teflon (PTFE)
Length
131 mm
Application temperature range
0 °C to +50 °C
Maximum false ceiling thickness
35 mm
Max. length of aspiration hose per
ceiling lead-through
1 m
Ceiling lead-through fitting material
ABS
Aspiration hose material
PE
Color of aspiration hose and ceiling
lead-through
White
Application temperature range
-40 °C to +80 °C
Summary of Contents for FCS-320-TM