background image

2

 

FCP-500

 

Series

 

Table

 

4:

 

Technical

 

Data

 

(continued)

 

Maximum

 

Thickness

 

of

 

False

 

Ceiling

 

1.25

 

in.

 

(32

 

mm),

 

flush

 

mount

 

applications

 

only

 

Minimum

 

Clearance

 

for

 

False

 

Ceiling

 

6

 

in.

 

(15.2

 

cm)

 

Required

 

Hole

 

5-

1

/

16

 

in.,

 

tolerance

 

-

1

/

16

 

in.

 

to

 

+

 

3

/

16

 

in.

 

(130

 

mm,

 

tolerance

 

-1

 

mm

 

to

 

+5

 

mm)

 

Minimum

 

Distance

 

from

 

Lamps

 

1.6

 

ft

 

(0.5

 

m)

 

Maximum

 

Airflow

 

300

 

ft/min

 

(1.5

 

m/s)

 

Operating

 

Temperature

 

+32

 

_

F

 

to

 

+100

 

_

F (0

 

_

C to

 

+38

 

_

C)

 

Humidity

 

<

 

95%,

 

non-condensing

 

Protection

 

Class

 

as

 

per

 

IEC

 

60529

 

- FCP-500-C

 

and

 

FCP-500-C-P

 

IP

 

33

 

- FCP-500

 

and

 

FCP-500-P

 

IP

 

53

 

Dimensions

 

- Detector

 

only

 

4.5

 

in.

 

x

 

2.2

 

in.

 

(113

 

mm

 

x

 

55

 

mm)

 

- Detector

 

with

 

Trim

 

Ring

 

5.9

 

in.

 

x

 

2.2

 

in.

 

(150

 

mm

 

x

 

55

 

mm)

 

- Detector

 

with

 

Trim

 

Ring

 

and

 

Base

 

5.9

 

in.

 

x

 

2.75

 

in.

 

(150

 

mm

 

x

 

70

 

mm)

 

with

 

base

 

Compliance

 

UL

 

268

 

2.

 

Installation

 

Considerations

 

i

 

For

 

proper

 

installation,

 

read

 

and

 

understand

 

NFPA-72,

 

The

 

National

 

Fire

 

Alarm

 

Code

 

be­

fore

 

installation.

 

Caution:

 

D

 

Do

 

not

 

remove

 

the

 

plastic

 

film

 

from

 

the

 

detector

 

head

 

until

 

construction

 

of

 

the

 

installation

 

area

 

is

 

finished.

 

D

 

Protect

 

the

 

detector

 

sensor

 

windows

 

from

 

paint

 

or

 

contaminates.

 

Remove

 

the

 

detector

 

head

 

during

 

remodelling

 

and

 

store

 

it

 

in

 

a

 

clean

 

dry

 

location.

 

.

 

If

 

you

 

do

 

not

 

follow

 

these

 

cautions,

 

the

 

detector

 

might

 

not

 

operate.

 

Detector

 

Location

 

and

 

Spacing:

 

D

 

BOSCH

 

recommends

 

spacing

 

the

 

sensors

 

in

 

compliance

 

with

 

NFPA-72.

 

In

 

low

 

air

 

flow

 

applications

 

with

 

smooth

 

ceilings,

 

space

 

sensors

 

with

 

a

 

maximum

 

distance

 

of

 

30

 

ft.

 

For

 

specific

 

information

 

regarding

 

sensor

 

spacing,

 

placement

 

and

 

special

 

application

 

refer

 

to

 

NFPA-72.

 

D

 

Not

 

suitable

 

for

 

outdoor

 

use.

 

D

 

Do

 

not

 

install

 

in

 

areas

 

where

 

the

 

detector

 

is

 

pointed

 

at

 

direct

 

or

 

indirect

 

sunlight.

 

D

 

Do

 

not

 

mount

 

detector

 

in

 

a

 

cone

 

of

 

light

 

from

 

a

 

lamp.

 

D

 

Maintain

 

a

 

hemispherical

 

radius

 

of

 

at

 

least

 

19

 

in.

 

(50

 

cm)

 

around

 

the

 

detector

 

(see

 

Fig.

 

1.).

 

Insure

 

that

 

this

 

area

 

in

 

front

 

and

 

to

 

the

 

sides

 

of

 

the

 

detector

 

is

 

kept

 

clear

 

of

 

all

 

obstructions

 

(see

 

Fig.

 

1.).

 

Further

 

Considerations:

 

D

 

Only

 

use

 

end-of-line

 

(EOL)

 

resistors

 

supplied

 

or

 

specified

 

by

 

the

 

control

 

panel

 

manufacturer.

 

D

 

Smoke

 

detectors

 

are

 

not

 

to

 

be

 

used

 

with

 

detector

 

guards

 

unless

 

the

 

combination

 

has

 

been

 

evaluated

 

and

 

found

 

suitable

 

for

 

that

 

purpose.

 

D

 

This

 

detector

 

must

 

be

 

installed

 

in

 

compliance

 

with

 

the

 

control

 

panel

 

system

 

installation

 

manual.

 

D

 

Install,

 

test

 

and

 

maintain

 

this

 

device

 

according

 

to

 

this

 

installation

 

guide,

 

NFPA-72,

 

Local

 

Codes

 

and

 

the

 

Authority

 

Having

 

Jurisdiction

 

(AHJ).

 

Failure

 

to

 

follow

 

these

 

procedures

 

may

 

cause

 

the

 

device

 

to

 

not

 

function

 

properly.

 

Bosch

 

Security

 

Systems

 

is

 

not

 

responsible

 

for

 

any

 

devices

 

that

 

are

 

improperly

 

installed,

 

tested

 

or

 

maintained.

 

Detector

 

19

 

in.

(50

 

cm

)

 

Ceiling

 

Free

 

space

 

Fig.

 

1.

 

BDL-F01U000626

 

|

 

A7

 

|

 

2007.07

 

Bosch

 

Security

 

Systems

 

                 Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Summary of Contents for FCP-500

Page 1: ...500 Series Photoelectric Detectors FCP 500 FCP 500 P FCP 500 C FCP 500 C P en Installation Guide Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Page 2: ...Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Page 3: ...tors 4 998 151 301 FAA 500 TR W Trim Ring White 4 998 151 295 FAA 500 TR P Trim Ring Transparent with Color Inserts 4 998 151 296 Table 3 Options optional Type Description Material No DRA 5 Remote LED Annunciator FAA 500 TTL Test Adapter with Magnet F 01U 508 725 FAA 500 RTL Removal Tool F 01U 508 720 Table 4 Technical Data Operating Voltage 9 7 V DC to 30 V DC Current Consumption Standby Alarm Tr...

Page 4: ...mpliance with NFPA 72 In low air flow applications with smooth ceilings space sensors with a maximum distance of 30 ft For specific information regarding sensor spacing placement and special application refer to NFPA 72 D Not suitable for outdoor use D Do not install in areas where the detector is pointed at direct or indirect sunlight D Do not mount detector in a cone of light from a lamp D Maint...

Page 5: ...r openings in the detector head are clearly exposed Ceiling Mount Back Box FAA 500 BB UL D For installation refer to the FAA 500 BB UL Installation Guide P N 601 F 01U 003 008 Wiring the Base FCA 500 and FCA 500 E i In applications which require UL listed units the power of all connections detector power trouble and alarm relay must be taken from power limited supplies when the cable is carried th...

Page 6: ...anel yellow Multiple Detector Wring to Power Supply FCA 500 black red FCA 500 to Control green Panel yellow blue yellow white white white Fig 6 black red FCA 500 E DRA 5 red white green blue white yellow Fig 7 BDL F01U000626 A7 2007 07 Bosch Security Systems Table 5 Wiring Connections Inner Ring for Conventional Connection Alar l Alarm m r re ela ay y normally open Shielding Indicator output Volta...

Page 7: ...t least 19 in 50 cm around these detectors If the problem persists replace these detectors or swap them with known good units If also the good units alarm or go in trouble the sensitivity may have been affected by the surrounding environment Recheck if there are any obstructions around the detector which may reflect the light emitted by the detector 5 Activate the dry reed contact of each detector...

Page 8: ... s performance X X 5 Perform Electronic Functional Test see Section 6 X X 6 Perform Sensitivity Test see Section 7 X X 7 Test the optical sensor see Section 8 X X 8 Test the optical sensor and the CO sensor see Section 9 X Table 7 LED Operation Status LED Normal green flashes every 8 sec Alarm red steady Trouble green double flash every 8 to12 sec Test mode green flashes once every second 5 Dry Re...

Page 9: ...r the detector might come loose 4 By covering the scattered light areas both optical sensors are triggered simultaneously no smoke aerosol is required 5 This can take up to 20 sec An alarm activates and the red LED lights If the panel is in test mode the alarm resets automatically 9 CO and Smoke Test for the FCP 500 C FCP 500 C P i The CO sensor has not been evaluated to the requirements of UL 207...

Page 10: ...Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 www boschsecurity us Customer Service 800 289 0096 Technical Support 888 886 6189 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Reviews: