2
FCP-500
Series
Table
4:
Technical
Data
(continued)
Maximum
Thickness
of
False
Ceiling
1.25
in.
(32
mm),
flush
mount
applications
only
Minimum
Clearance
for
False
Ceiling
6
in.
(15.2
cm)
Required
Hole
5-
1
/
16
in.,
tolerance
-
1
/
16
in.
to
+
3
/
16
in.
(130
mm,
tolerance
-1
mm
to
+5
mm)
Minimum
Distance
from
Lamps
1.6
ft
(0.5
m)
Maximum
Airflow
300
ft/min
(1.5
m/s)
Operating
Temperature
+32
_
F
to
+100
_
F (0
_
C to
+38
_
C)
Humidity
<
95%,
non-condensing
Protection
Class
as
per
IEC
60529
- FCP-500-C
and
FCP-500-C-P
IP
33
- FCP-500
and
FCP-500-P
IP
53
Dimensions
- Detector
only
4.5
in.
x
2.2
in.
(113
mm
x
55
mm)
- Detector
with
Trim
Ring
5.9
in.
x
2.2
in.
(150
mm
x
55
mm)
- Detector
with
Trim
Ring
and
Base
5.9
in.
x
2.75
in.
(150
mm
x
70
mm)
with
base
Compliance
UL
268
2.
Installation
Considerations
i
For
proper
installation,
read
and
understand
NFPA-72,
The
National
Fire
Alarm
Code
be
fore
installation.
Caution:
D
Do
not
remove
the
plastic
film
from
the
detector
head
until
construction
of
the
installation
area
is
finished.
D
Protect
the
detector
sensor
windows
from
paint
or
contaminates.
Remove
the
detector
head
during
remodelling
and
store
it
in
a
clean
dry
location.
.
If
you
do
not
follow
these
cautions,
the
detector
might
not
operate.
Detector
Location
and
Spacing:
D
BOSCH
recommends
spacing
the
sensors
in
compliance
with
NFPA-72.
In
low
air
flow
applications
with
smooth
ceilings,
space
sensors
with
a
maximum
distance
of
30
ft.
For
specific
information
regarding
sensor
spacing,
placement
and
special
application
refer
to
NFPA-72.
D
Not
suitable
for
outdoor
use.
D
Do
not
install
in
areas
where
the
detector
is
pointed
at
direct
or
indirect
sunlight.
D
Do
not
mount
detector
in
a
cone
of
light
from
a
lamp.
D
Maintain
a
hemispherical
radius
of
at
least
19
in.
(50
cm)
around
the
detector
(see
Fig.
1.).
Insure
that
this
area
in
front
and
to
the
sides
of
the
detector
is
kept
clear
of
all
obstructions
(see
Fig.
1.).
Further
Considerations:
D
Only
use
end-of-line
(EOL)
resistors
supplied
or
specified
by
the
control
panel
manufacturer.
D
Smoke
detectors
are
not
to
be
used
with
detector
guards
unless
the
combination
has
been
evaluated
and
found
suitable
for
that
purpose.
D
This
detector
must
be
installed
in
compliance
with
the
control
panel
system
installation
manual.
D
Install,
test
and
maintain
this
device
according
to
this
installation
guide,
NFPA-72,
Local
Codes
and
the
Authority
Having
Jurisdiction
(AHJ).
Failure
to
follow
these
procedures
may
cause
the
device
to
not
function
properly.
Bosch
Security
Systems
is
not
responsible
for
any
devices
that
are
improperly
installed,
tested
or
maintained.
Detector
19
in.
(50
cm
)
Ceiling
Free
space
Fig.
1.
BDL-F01U000626
|
A7
|
2007.07
Bosch
Security
Systems