background image

                 Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Summary of Contents for FCP-500

Page 1: ...500 Series Photoelectric Detectors FCP 500 FCP 500 P FCP 500 C FCP 500 C P en Installation Guide Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Page 2: ...Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Page 3: ...tors 4 998 151 301 FAA 500 TR W Trim Ring White 4 998 151 295 FAA 500 TR P Trim Ring Transparent with Color Inserts 4 998 151 296 Table 3 Options optional Type Description Material No DRA 5 Remote LED Annunciator FAA 500 TTL Test Adapter with Magnet F 01U 508 725 FAA 500 RTL Removal Tool F 01U 508 720 Table 4 Technical Data Operating Voltage 9 7 V DC to 30 V DC Current Consumption Standby Alarm Tr...

Page 4: ...mpliance with NFPA 72 In low air flow applications with smooth ceilings space sensors with a maximum distance of 30 ft For specific information regarding sensor spacing placement and special application refer to NFPA 72 D Not suitable for outdoor use D Do not install in areas where the detector is pointed at direct or indirect sunlight D Do not mount detector in a cone of light from a lamp D Maint...

Page 5: ...r openings in the detector head are clearly exposed Ceiling Mount Back Box FAA 500 BB UL D For installation refer to the FAA 500 BB UL Installation Guide P N 601 F 01U 003 008 Wiring the Base FCA 500 and FCA 500 E i In applications which require UL listed units the power of all connections detector power trouble and alarm relay must be taken from power limited supplies when the cable is carried th...

Page 6: ...anel yellow Multiple Detector Wring to Power Supply FCA 500 black red FCA 500 to Control green Panel yellow blue yellow white white white Fig 6 black red FCA 500 E DRA 5 red white green blue white yellow Fig 7 BDL F01U000626 A7 2007 07 Bosch Security Systems Table 5 Wiring Connections Inner Ring for Conventional Connection Alar l Alarm m r re ela ay y normally open Shielding Indicator output Volta...

Page 7: ...t least 19 in 50 cm around these detectors If the problem persists replace these detectors or swap them with known good units If also the good units alarm or go in trouble the sensitivity may have been affected by the surrounding environment Recheck if there are any obstructions around the detector which may reflect the light emitted by the detector 5 Activate the dry reed contact of each detector...

Page 8: ... s performance X X 5 Perform Electronic Functional Test see Section 6 X X 6 Perform Sensitivity Test see Section 7 X X 7 Test the optical sensor see Section 8 X X 8 Test the optical sensor and the CO sensor see Section 9 X Table 7 LED Operation Status LED Normal green flashes every 8 sec Alarm red steady Trouble green double flash every 8 to12 sec Test mode green flashes once every second 5 Dry Re...

Page 9: ...r the detector might come loose 4 By covering the scattered light areas both optical sensors are triggered simultaneously no smoke aerosol is required 5 This can take up to 20 sec An alarm activates and the red LED lights If the panel is in test mode the alarm resets automatically 9 CO and Smoke Test for the FCP 500 C FCP 500 C P i The CO sensor has not been evaluated to the requirements of UL 207...

Page 10: ...Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 www boschsecurity us Customer Service 800 289 0096 Technical Support 888 886 6189 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Reviews: