Technical Data
DO detectors
Detector Type
FAP-DOTC420
FAP-DOT420
FAP-DO420
Detection principle
Combination of:
–
Scattered-light measurement
–
Measurement of absolute
temperature and temperature
increase
Scattered-light
measurement
–
Combustion
gas
measurement
-
-
Special features
–
Two optical sensors
–
Contamination detection
–
Drift compensation in the optical sensor
–
Operation switching/sensor
deactivation in the optical unit and
in the thermal unit
-
Operating voltage
15 V DC to 33 V DC
Current consumption
< 0.55 mA
Individual display
Two-color LED (red/green)
Alarm output
Per data word by two-wire signal line
Indicator output
Open collector connects 0 V over 1.5 kilohm, max. 15 mA
Response sensitivity (basic
data)
Optical sensor
< 0.18 dB/m (EN 54-7)
Thermal sensor
EN 54-5
-
–
Thermal differential
unit
-
–
Thermal maximum unit > 54 °C/> 69 °C
-
Chemical sensor
ppm range
-
-
Max. monitoring area
120 m
2
(observe VdS guidelines)
Max. installation height
16 m (observe VdS guidelines)
Permitted air speed
20 m/s
Permissible operating
temperature
-10 °C. . . +50 °C
-20 °C. . . +50 °C
-20 °C. . . +65 °C
Permitted relative humidity
< 95% (non-condensing)
Protection category
according to EN 60529
IP 40/IP 43 with detector base with damp room seal
9
Automatic Fire Detectors LSN
improved
Technical Data | en
43
Bosch Sicherheitssysteme GmbH
Operation Guide
12/2012 | 8.1 | F.01U.003.448
Summary of Contents for FAH-420
Page 1: ...Automatic Fire Detectors LSN improved FAP DO420 FAP 420 FAH 420 en Operation Guide ...
Page 2: ......
Page 48: ......
Page 49: ......