D1255RB/D1256RB/D1257RB | Installation Guide | 4.0 D1256RB Programming Requirements
.
Bosch Security Systems B.V. | 2020.03 | F01U011791-03
13
4.4.1 Menu Item and Function
Program the first ten menu items as indicated in
Table 3
. This programming is necessary for the
D1256RB to operate properly. The first four keys
on the D1256RB execute the first four menu
items enabled at the keypad address. Menu
items five through ten are optional features that
can be programmed into the D1256RB system.
Refer to the
Fire System User’s Guide
(P/N:
F01U011793) for further explanation of these
optional programmable items.
Ensure that
CF 128
through
CF 131
are programmed E (enabled) and not
P (passcode required).
Table 3: Function List Description
Menu Item
Shortcut menu
1
Function
Description
1
128
ALARM SILENCE?
2
129
TROUBLE SILENCE?
3
130
DETECTOR RESET?
4
131
ANNUNCIATOR RESET
5
9
VIEW MEMORY?
6
10
VIEW PT STATUS?
7
12
FIRE TEST?
8
21
VIEW LOG?
9
29
REMOTE PROGRAM?
10
32
DISPLAY REV?
1
D9412GV4/D7412GV4/D7212GV4 v2.xx or later
1
Use the ESC key to access the Shortcut menu. Use Next and
Prev to navigate the Shortcut menu.
4.4.2 CC Address #
CC = command center = keypad
Program the keypad (command center)
addresses as Yes for the first four menu items
and for the optionally programmed menu items
5 through 10.