Outdoor Unit Installation
1. Prepare the cable for connection:
USE THE CORRECT CABLE
•
Indoor Power Cable
(if applicable): H05VV-F or H05V2V2-F
•
Outdoor Power Cable
: H07RN-F
•
Signal Cable
: H07RN-F
Minimum Cross-Sectional Area of Power and Signal Cables
•
UK
Rated Current of Appliance
(A)
Nominal Cross-Sectional Area
(mm²)
> 3 and ≤ 6
0.75
> 6 and ≤ 10
1
> 10 and ≤ 16
1.5
> 16 and ≤ 25
2.5
> 25 and ≤ 32
4
> 32 and ≤ 40
6
Table 4.
a. Using wire strippers, strip the rubber jacket from both ends of cable
to reveal about 40mm of the wires inside.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp u-lugs on the ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly distinguish the Live (“L”)
Wire from other wires.
WARNING
ALL WIRING MUST INSTALLED STRICTLY IN ACCORDANCE WITH
THE WIRING DIRGRAM LOCATED INSIDE THE OUTDOOR UNIT’S
WIRE COVER.
2. Unscrew the electrical wiring cover and remove it.
3. Unscrew the cable clamp below the terminal block and place it to
the side.
4. Match the wire colours/labels with the labels on the terminal
block and firmly screw the u-lug of each wire to its corresponding
terminal.
5. After checking ensure every connection is secure, loop the wires
around to prevent rain water from flowing into the terminal.
6. Using the cable clamp, fasten the cable to the unit. Screw the cable
clamp down tightly.
7. Insulate unused wires with PVC electrical tape. Arrange them so that
they do not touch any electrical or metal parts.
8. Replace the wire cover on the side of the unit and screw down.
Cover
Outdoor Unit Wiring Diagram is located on
the inside of the wire cover on the outdoor
unit.
Fig. 26.