background image

16

 

Climate 5000 – 6720886909 (2018/04)

 Outdoor Unit Installation

Outdoor unit dimension  

mm (WxHxD)

Mounting dimensions
Distance A 

(mm)

Distance B 

(mm)

681x434x285

460

292

700x550x270

450

260

780x540x250

549

276

845x700x320

560

335

810x558x310

549

325

700x550x275

450

260

770x555x300

487

298

800x554x333

514

340

845x702x363

540

350

900x860x315

590

333

945x810x395

640

405

946x810x420

673

403

946x810x410

673

403

Table 3. 

If you install the unit on the ground or on a concrete mounting 

platform

, do the following:

1.  Mark the positions for four expansion bolts based on dimensions in 

the Unit Mounting Dimensions chart.

2.  Pre-drill holes for expansion bolts.
3.  Clean concrete dust away from holes.
4.  Place a nut on the end of each expansion bolt.
5.  Hammer expansion bolts into the pre-drilled holes.
6.  Remove the nuts from expansion bolts and place outdoor unit on 

bolts.

7.  Put washer on each expansion bolt, then replace the nuts.
8.  Using a wrench, tighten each nut until snug.

WARNING

WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOM-

MENDED AT ALL TIMES.

If you install the unit on a wall-mounted bracket

, do the following:

CAUTION

Before installing a wall-mounted unit, ensure  that the wall is made of 

solid brick, concrete or of similarly strong material. 

The wall must be 

able to support at least four times the weight of the unit.

1.  Mark the position of bracket holes based on dimensions in the Unit 

Mounting Dimensions chart.

2.  Pre-drill the holes for the expansion bolts.
3.  Clean dust and debris away from holes.
4.  Place a washer and nut on the end of each expansion bolt.
5.  Thread expansion bolts through holes in mounting brackets, put 

mounting brackets in position and hammer expansion bolts into the 

wall.

6.  Check that the mounting brackets are level.
7.  Carefully lift unit and place its mounting feet on brackets.

8.  Bolt the unit firmly to the brackets.

To reduce vibrations of wall- mounted unit

If allowed, you can install the wall-mounted unit with rubber gaskets to 

reduce vibrations and noise.

1.12  Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by an electrical wiring 

cover on the side of the unit. A comprehensive wiring diagram is printed 

on the inside of the wiring cover.

WARNING

Before performing electrical work, read these guidelines

1.  All wiring must comply with local and national electrical codes and 

must be installed by a licensed electrician.

2.  All electrical connections must be made according to the Electrical 

Connection Diagram located on the side panels of the indoor and 

outdoor units.

3.  If there is a serious safety issue with the power supply, stop work 

immediately. Explain your reasoning to the client and refuse to 

install the unit until the safety issue is properly resolved.

4.  Power voltage should be within 90-110% of rated voltage. 

Insufficient power supply can cause electrical shock or fire.

5.  If connecting power to fixed wiring, install a surge protector and 

main power switch with a capacity of 1.5 times the maximum 

current of the unit.

6.  If connecting power to fixed wiring, a switch or circuit breaker that 

disconnects all poles and has a contact separation of at least 3mm 

must be incorporated in the fixed wiring. The qualified technician 

must use an approved circuit breaker or switch.

7.  Only connect the unit to an individual branch circuit outlet. Do not 

connect another appliance to that outlet.

8.  Ensure to correctly ground the air conditioner.
9.  All cables must be firmly connected. Loose wiring can cause the 

terminal to overheat, resulting in product malfunction and possible 

fire.

10. Do not

 let wires touch or rest against refrigerant tubing, the 

compressor or any moving parts within the unit.

11. If the unit has an auxiliary electric heater, it must be installed at 

least 1 metre away from any combustible materials.

WARNING

BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, ISO-

LATE THE MAIN POWER TO THE SYSTEM.

Summary of Contents for Climate 5000 RAC 2,6-2 IBW

Page 1: ... 5000 RAC 2 6 2 IBW OU OUE RAC 3 5 2 IBW OU OUE RAC 5 3 2 IBW OU OUE RAC 7 2 IBW OU OUE Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference ...

Page 2: ...air or maintenance of this unit 4 Only use the included accessories parts and specified parts for installation Using non standard parts can cause water leakage electric shock fire and can cause the unit to fail 5 Install the unit in a firm location that can support the unit s weight If the chosen location cannot support the unit s weight or is not installed correctly the unit may drop and cause se...

Page 3: ...commended 15 If the supply cable is damaged it must be replaced by Qualified Personnel in order to avoid a hazard CAUTION For units that have an auxiliary electric heater do not install the unit within 1 metre of any combustible materials Do not install the unit in a location that may be exposed to combustible gases If combustible gas accumulates around the unit it may cause fire Do not operate yo...

Page 4: ...rew for remote controller holder ST2 9 x 10 2 Remote controller holder 1 Dry battery AAA 2 Seal 1 Drain joint Owner s manual SPLIT TYPE ROOM AIR CONDITIONER CS78421 548 754 IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Owner s Manual Forest Series All Model Numbers 1 Installation manual SPL...

Page 5: ...ust purchase Ø9 52 Gas side Ø9 52 Ø12 7 Ø16 Ø19 Table 1 WARNING Appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation For R32 refrigerant models Appliance shall be installed operated and stored in a room with a floor area larger than 4m2 Appliance shall not be installed in an unventilated space if that space is smaller than ...

Page 6: ...18 04 Installation Summary Indoor Unit 3 Installation Summary Indoor Unit 1 2 3 4 15cm 12cm Select Installation Location Page 11 Attach Mounting Plate Page 12 Determine Wall Hole Position Page 12 Drill Wall Hole Page 12 12cm 2 3m ...

Page 7: ...limate 5000 6720886909 2018 04 7 Installation Summary Indoor Unit STEP8 5 6 7 8 9 Connect Piping Page 25 Wrap Piping and Cable Mount Indoor Unit Page 18 Connect Wiring Page 17 Prepare Drain Hose Page 14 ...

Page 8: ... 5 Power isolator Fig 1 1 Wall Mounting Plate 2 Front Panel 3 Power Cable Some Units 4 Louver 5 Functional Filter On Front of Main Filter Some Units 6 Drainage Pipe 7 Signal Cable 8 Refrigerant Piping 9 Remote Controller 10 Remote Controller Holder Some Units 11 Outdoor Unit Power Cable Some Units NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of y...

Page 9: ...p 2 Attach mounting plate to wall Themountingplateisthedeviceonwhichyouwillmounttheindoorunit 1 Remove the screw that attaches the mounting plate to the back of the indoor unit 2 Place the mounting plate against the wall in a location that meets the standards in the Select Installation Location step See Mounting Plate Dimensions for detailed information on mounting plate sizes 3 Drill holes for mo...

Page 10: ...ht rear wall hole 65mm Indoor unit outline 439mm 958 3mm 224 2mm 228 5mm 285mm 45mm 259 1mm 100 6mm 47mm 47 5mm 36 7mm 36 6mm 123 7mm Fig 8 Model D Left rear wall hole 65mm Right rear wall hole 65mm 506mm 1037 6mm 291mm 316 7mm 324 9mm 47mm 47mm 55mm 55mm 246mm 271 7mm Fig 9 NOTE When the gas side connective pipe is Ø16mm or more the wall hole should be 90mm 1 4 Step 4 Prepare refrigerant piping T...

Page 11: ...not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance 1 5 Step 5 Connect drain hose By default the drain hose is attached to the left hand side of unit when you re facing the back of the unit However it can also be attached to the right hand side 1 To ensure proper drainage attach the drain hose on the same side that your ...

Page 12: ... tubing the compressor or any moving parts within the unit 11 If the unit has an auxiliary electric heater it must be installed at least 1 metre away from any combustible materials WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK ISOLATE MAIN POWER TO THE SYSTEM 1 6 Step 6 Connect signal cable The signal cable enables communication between the indoor and outdoorunits Youmustfirstchoosetheri...

Page 13: ...unit Indoor Unit Fig 17 Drain hose must be on bottom Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lead to fire or water damage Do not intertwine signal cable with other wires While bundling wiring together do not intertwine or cross the signal cable with any other wiring 2 Using adhesive v...

Page 14: ...ded pipes to the indoor unit the unit can be adjusted left or right by about 30 50mm depending on the model See Fig 19 30 50mm 30 50mm Move to left or right Fig 19 6 Outdoor Unit Installation Fig 20 Installation Instructions Outdoor Unit 1 9 Step 1 Select installation location Before installing the outdoor unit you must choose an appropriate location The following are standards that will help you ...

Page 15: ...eal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks into place facing the front of the unit 4 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode If the drain joint does not come with a rubber seal see Fig ...

Page 16: ...ets To reduce vibrations of wall mounted unit If allowed you can install the wall mounted unit with rubber gaskets to reduce vibrations and noise 1 12 Step 4 Connect signal and power cables The outside unit s terminal block is protected by an electrical wiring cover on the side of the unit A comprehensive wiring diagram is printed on the inside of the wiring cover WARNING Before performing electri...

Page 17: ...sh the Live L Wire from other wires WARNING ALL WIRING MUST INSTALLED STRICTLY IN ACCORDANCE WITH THE WIRING DIRGRAM LOCATED INSIDE THE OUTDOOR UNIT S WIRE COVER 2 Unscrew the electrical wiring cover and remove it 3 Unscrew the cable clamp below the terminal block and place it to the side 4 Match the wire colours labels with the labels on the terminal block and firmly screw the u lug of each wire ...

Page 18: ...3 Make sure that the pipe is cut at a perfect 90 angle Refer to Fig 28 for bad cut examples 90 Oblique Rough Warped Fig 28 WARNING DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit 1 14 2 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They mu...

Page 19: ... unit then the outdoor unit Minimum bend radius When bending connective refrigerant piping the minimum bending radius is 10cm See Fig 33 Radius 10cm Fig 33 Instructions for Connecting Piping to Indoor Unit 1 Align the centre of the two pipes that you will connect See Fig 34 Indoor unit tubing Flare nut Pipe Fig 34 2 Tighten the flare nut as tightly as possible by hand 3 Using a spanner grip the nu...

Page 20: ...rotective caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 37 WARNING USE SPANNER TO GRIP MAIN BODY OF VALVE Torque from over tightening the flare nut can snap off other parts of valve Fig 37 5 While firmly gripping the body ...

Page 21: ...vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 105 Pa 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for leaks If there is no change in system pressure un...

Page 22: ...acuum Pump Liquid Side Ø 6 35 R32 Pipe length standard length x 12g m Pipe length standard length x 0 13oZ ft R410A Pipe length standard length x 15g m Pipe length standard length x 0 16oZ ft Liquid Side Ø 9 52 R32 Pipe length standard length x 24g m Pipe length standard length x 0 26oZ ft R410A Pipe length standard length x 30g m Pipe length standard length x 0 32oZ ft Table 8 CAUTION DO NOT mix ...

Page 23: ...that the unit s electrical system is safe and operating properly Gas Leak Checks Check all flare nut connections and confirm that the system is not leaking Confirmthatgasandliquid highandlowpressure valvesarefullyopen Test Run Instructions You should perform the Test Run for at least 30 minutes 1 Connect power to the unit 2 Press the ON OFF button on the remote controller to turn it on 3 Press the...

Page 24: ...ropean Disposal Guidelines This appliance contains refrigerant and other potentially hazardous materials When disposing of this appliance the law requires special collection and treatment Do not dispose of this product as household waste or unsorted municipal waste When disposing of this appliance you have the following options Dispose of the appliance at designated municipal electronic waste coll...

Page 25: ...d if an indirect refrigerating circuit is being used the secondary circuits should be checked for the presence of refrigerant marking to the equipment continues to be visible and legible marking and signs that are illegible should be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing...

Page 26: ...ossible to minimize the amount of refrigerant contained in them Cylinders must be kept upright Ensure that the refrigeration system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extreme care should be taken not to overfill the refrigeration system Prior to recharging the system it must be pressure tested with OFN The system must ...

Page 27: ... removed ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process should be carried out prior to returning the compressor to the suppliers Only electric heating to the compres sor body should be employed to accelerate this process When oil is drained from a system it should be carried out safe...

Page 28: ...Bosch Thermotechnology Ltd Cotswold Way Warndon Worcester WR4 9SW mailto Commercial enquiry uk bosch com Contact Number 03301233004 Web address www bosch industrial co uk ...

Reviews: