Backdraft reducer
The Heat Fab backdraft reducer (9301BFP) is the pre-
ferred option for limiting backdraft (see Fig. 20).
Note: The following solution is available only for
3" diameter venting.
Fig. 20 Part nr 9301BFP
Installation
For this solution to be effective, the internal flapper must
be 100% closed when the water heater is not running.
Refer to Figures 22 and 23 for preferred installation
positions in the vent system.
Installation considerations:
• Install damper per the supplied manufacturer‘s
instructions.
• The damper is only to be used in the exhaust vent
piping.
• Ensure directional arrow on damper label faces in the
same direction as exhaust flow.
• If installed horizontally, the axis must be horizontal or
slightly pitched up towards termination to ensure
damper closes 100% when heater is not running.
• To allow accessibility, damper must not be installed
in an enclosed section of vent pipe.
• Do not install damper in unconditioned spaces (e.g.
attics) Condensation can build up while the heater is
running which can later freeze and potentially block
the flapper.
Fig. 21 Blackflow reducer (9301BFP) installed
Fig. 22
Fig. 23
6720608643-18.1V
6720608643-19.1V
6720608542-06.2V
Preferred damper position for vertical terminations
Unconditioned
space. Do not
install damper.
Enclosed vent
pipe. Do not
install damper.
6720608836-30.2V
Summary of Contents for C1050ES
Page 56: ...6 720 646 812 56 Functional scheme 11 Functional scheme Fig 76 Functional scheme ...
Page 58: ...6 720 646 812 58 Interior components diagram and parts list Fig 78 Appliance overview ...
Page 69: ...6 720 646 812 Notes 69 15 Notes ...
Page 70: ...6 720 646 812 70 Notes ...
Page 71: ...6 720 646 812 Notes 71 ...